2003-07-25 00:00:00PASSED/PROVISO
  
 SHT P-103 LOCKER ROOM SANITARY/VENT
 RISER, HORIZONTAL DRY VENT NOT APPROVED.
 WATER CLOSET SHALL TIE IN ON THE VERTIC-
 AL RISE. SECTION 905.3- REVISION REQD.
  
 SHT P-301 VALVES REQUIRED ON WATER RISER
 SECTION 606.1(4)
 SHT P-407 VALVES REQUIRED ON WATER RISER
 SECTION 606.1(4)
  
 SHT P-409 VENTS AND LAV ARM NOT SHOWN ON
 RISER "B" REVISION REQUIRED.
  
  
 --GAS PERMIT APPLICATION REQUIREMENTS---
 WELDER'S CERTIFICATION, PICTURE I.D. AND
 WELDING PROCEDURE REQUIRED PRIOR TO
 ISSUING OF GAS PERMIT.
 WELDING INSPECTIONS REQUIRED: TACK-UP,
 ROOT PASS, FILLER PASS. COVER PASS CAN
 BE INSPECTED AT TIME OF ROUGH INSPECTION
 SHUT OFF VALVES UPSTREAM OF REGULATORS
 REQUIRED AT EACH GAS FIXTURE. UNION RE-
 QUIRED DOWNSTREAM OF REGULATOR. PIPE
 SIZES TO BE CORRECTED AT 750,000 BTU
 HEATERS. 2" REQUIRED. PIPE SIZES NOT
 SHOWN ADJACENT TO METER. SUBMIT A REVIS-
 ED GAS RISER WITH THESE CORRECTIONS WITH
 GAS APPLICATION.
 MANUFACTURE CUT SHEET REQUIRED FOR THE
 REGULATORS, DISHWASHER, UDS EQUIPMENT.
 CUT SHEETS FOR GAS APPLIANCES SHALL SHOW
 A LISTING BY AN APPROVED AGENCY AND BTU
 LOAD FOR EACH APPLIANCE. (LOCHIVAR UNITS
 DO NOT SHOW A LISTING)
  