2003-07-25 00:00:00 | PASSED/PROVISO |
| |
| SHT P-103 LOCKER ROOM SANITARY/VENT |
| RISER, HORIZONTAL DRY VENT NOT APPROVED. |
| WATER CLOSET SHALL TIE IN ON THE VERTIC- |
| AL RISE. SECTION 905.3- REVISION REQD. |
| |
| SHT P-301 VALVES REQUIRED ON WATER RISER |
| SECTION 606.1(4) |
| SHT P-407 VALVES REQUIRED ON WATER RISER |
| SECTION 606.1(4) |
| |
| SHT P-409 VENTS AND LAV ARM NOT SHOWN ON |
| RISER "B" REVISION REQUIRED. |
| |
| |
| --GAS PERMIT APPLICATION REQUIREMENTS--- |
| WELDER'S CERTIFICATION, PICTURE I.D. AND |
| WELDING PROCEDURE REQUIRED PRIOR TO |
| ISSUING OF GAS PERMIT. |
| WELDING INSPECTIONS REQUIRED: TACK-UP, |
| ROOT PASS, FILLER PASS. COVER PASS CAN |
| BE INSPECTED AT TIME OF ROUGH INSPECTION |
| SHUT OFF VALVES UPSTREAM OF REGULATORS |
| REQUIRED AT EACH GAS FIXTURE. UNION RE- |
| QUIRED DOWNSTREAM OF REGULATOR. PIPE |
| SIZES TO BE CORRECTED AT 750,000 BTU |
| HEATERS. 2" REQUIRED. PIPE SIZES NOT |
| SHOWN ADJACENT TO METER. SUBMIT A REVIS- |
| ED GAS RISER WITH THESE CORRECTIONS WITH |
| GAS APPLICATION. |
| MANUFACTURE CUT SHEET REQUIRED FOR THE |
| REGULATORS, DISHWASHER, UDS EQUIPMENT. |
| CUT SHEETS FOR GAS APPLIANCES SHALL SHOW |
| A LISTING BY AN APPROVED AGENCY AND BTU |
| LOAD FOR EACH APPLIANCE. (LOCHIVAR UNITS |
| DO NOT SHOW A LISTING) |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |