Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
B |
Sequence Number |
40 |
|
Notes |
Date |
Text |
2004-04-13 00:00:00 | ****CORRECTIONS**** | | STEEL TRUSS, MECH RM STAIR, | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | ************************************** | | STEEL TRUSS ENGINEERING PREPARED BY | | KEYMARK ENGINEERING, TS CHEHAL PE DATED | | 2/25/04, WESTERN AL ROOF SHOPS | | SUBMITTAL #05D-07-05210-1 | | | | 1.)THE AUTHORIZATION NUMBER FOR | | KEYMARK IS TO BE ON EACH SHEET.THE | | PRINTED NAME AND LICENSE NUMBER OF THE | | PERSON SEALING THE PLAN IS TO BE ON | | EACH SHEET.FAC61G15-23.002. | | *************************************** | | | | ROOF TOP MECH ROOM STAIR, PREPARED BY | | A.MARK SCALA, PE DATED 2/6/04 | | SUBMITTAL 05A-20-05500-0 | | | | 1.)THE TITLE BLOCK IS TO BE ON EACH | | SHEET, AND IS TO INCLUDE THE ADDRESS, | | COMPANY NAME, CA NUMBER. | | THE PRINTED NAME AND LICENSE NUMBER OF | | THE PERSON SEALING THE DOCUMENT IS TO | | BE ON EACH SHEET. | | | | 2.)PROVIDE CALCS FOR THE HANDRAIL TO | | COMPLY WITH FBC1608.2.1.PROVIDE CALCS | | FOR THE GUARDRAIL/STAIRRAIL TO COMPLY | | WITH FBC1608.2.2. | | | | ************************************** | | | | CC:DON NEELY |
|