2003-07-16 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FBC-2001 FUEL GAS |
| FHA-AMEND 98 DESIGN MANUAL |
| |
| 1) SHTS A2.02A, A-2.03A, & A-2.3, THE |
| VERANDA ROOF DRAINS SHOW NO PIPING. IN- |
| DICATE HOW THE RAIN WATER WILL BE DRAIN- |
| ED OFF THIS ROOF AND WHERE IT WILL TER- |
| MINATE. ALSO THERE APPEARS TO BE A PARA- |
| PET WALL THAT WILL NEED A SCUPPER. IF SO |
| PLEASE SHOW WHERE THE SCUPPER WILL BE |
| LOCATED AND INDICATE THE SIZE. |
| 2) SHT P-409 DOES NOT REFLECT THE FLOOR |
| PLAN. IN WOMEN'S LOCKER ROOM THE FLOOR |
| PLAN SHOWS A WATER CLOSET, LAV IN STALL, |
| THEN TWO MORE WATER CLOSETS, AND THEN |
| THE DRINKING FOUNTAIN IN THE CORRIDOR. |
| THE RISER DIAGRAM SHOWS TWO 4" LINES FOR |
| W/C'S THEN THREE 2" LINES PRIOR TO THE |
| DRINKING FOUNTAIN. ALSO 8" REQUIREDON |
| SANITARY BY NEW CLEANOUT AS SHOWN IN |
| PREVIOUS COMMENT. |
| 3) SHT P-410 SEWER "G" 2 LINES SHOWN FOR |
| RISERS B/15 & KS/33 ON FLOOR PLAN BUT |
| ONLY ONE SHOWN ON RISER DIAGRAM. |
| SEWER "F" KS/31 MISSING |
| FROM RISER DIAGRAM. |
| SEWER "H" VENT REQUIRED |
| PRIOR TO FIRST FLOOR DRAIN. - PER TABLE |
| 906.1 TRAP SHALL BE MAXIMUM OF 12' FROM |
| VENT, 4" HUB DRAIN IS APPROX. 16'. ALSO |
| RISERS B/49, B/57, B-51, B/52, KS/32, & |
| KS/33 NOT ON FLOOR PLAN. |
| SEWER "F" RISER W/22 NOT |
| FOUND WITH OTHER RISERS. SUBMIT RISER. |
| FIXTURE UNITS/PIPE SIZE NOT CORRECT AS |
| INDICATED IN PREVIOUS REVIEW. |
| SEWER "D" PIPE SIZE FOR |
| 4,970 S.F. REQUIRES 8" PIPE. 6" SHOWN. |
| PIPE SIZE FOR 783 S.F. REQUIRES 4" PIPE |
| ON THE HORIZONTAL. 3" SHOWN. |
| PIPE SIZE FOR 778 S.F. REQUIRES 4" PIPE |
| ON THE HORIZONTAL. 3" SHOWN. |
| 4) SHTS P-202 & P-405 - 6" HUB DRAIN |
| SHOWN TO BOTH SANITARY AND TO STORM. |
| DELETE FROM SANITARY SYSTEM ON BOTH |
| SHEETS. |
| 5) SHT P-202 NO SANITARY TO LAV IN HDCP |
| STALL MEN'S LOCKER ROOM. |
| 6) SHT P-203 OVERFLOW FROM THE COOLING |
| TOWER SHALL DRAIN TO STORM. THE COOLING |
| TOWER SHALL DRAIN TO SANITARY. |
| 7) PLANS HAVE NOT BEEN ROUTED TO THE |
| PALM BEACH HEALTH UNIT. THIS SHALL BE |
| DONE PRIOR TO ISSUING A PERMIT. |
| 8) SHTS A-2.14, A-2.42, & A-2.43 MANUF. |
| INFORMATION REQUIRED FOR SHOWERS TO |
| VERIFY COMPLIANCE WITH HEIGHT OF GRAB |
| BARS PER FHA DESIGN MANUAL. |
| 9) SHT A-8.11 TOILET ROOM DOORS SHALL |
| NOT OPEN INTO THE CLEAR FLOOR SPACE OF |
| THE TURNING RADIUS. SEC 11-4.22.2 |
| 10 SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| ONLY WATER HEATER SHEETS SUBMITTED. |
| |
| REVIEW BY KEN STEVENS |