Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop P
Sequence Number 4
Notes
Date Text
2003-07-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHTS A2.02A, A-2.03A, & A-2.3, THE
 VERANDA ROOF DRAINS SHOW NO PIPING. IN-
 DICATE HOW THE RAIN WATER WILL BE DRAIN-
 ED OFF THIS ROOF AND WHERE IT WILL TER-
 MINATE. ALSO THERE APPEARS TO BE A PARA-
 PET WALL THAT WILL NEED A SCUPPER. IF SO
 PLEASE SHOW WHERE THE SCUPPER WILL BE
 LOCATED AND INDICATE THE SIZE.
 2) SHT P-409 DOES NOT REFLECT THE FLOOR
 PLAN. IN WOMEN'S LOCKER ROOM THE FLOOR
 PLAN SHOWS A WATER CLOSET, LAV IN STALL,
 THEN TWO MORE WATER CLOSETS, AND THEN
 THE DRINKING FOUNTAIN IN THE CORRIDOR.
 THE RISER DIAGRAM SHOWS TWO 4" LINES FOR
 W/C'S THEN THREE 2" LINES PRIOR TO THE
 DRINKING FOUNTAIN. ALSO 8" REQUIREDON
 SANITARY BY NEW CLEANOUT AS SHOWN IN
 PREVIOUS COMMENT.
 3) SHT P-410 SEWER "G" 2 LINES SHOWN FOR
 RISERS B/15 & KS/33 ON FLOOR PLAN BUT
 ONLY ONE SHOWN ON RISER DIAGRAM.
 SEWER "F" KS/31 MISSING
 FROM RISER DIAGRAM.
 SEWER "H" VENT REQUIRED
 PRIOR TO FIRST FLOOR DRAIN. - PER TABLE
 906.1 TRAP SHALL BE MAXIMUM OF 12' FROM
 VENT, 4" HUB DRAIN IS APPROX. 16'. ALSO
 RISERS B/49, B/57, B-51, B/52, KS/32, &
 KS/33 NOT ON FLOOR PLAN.
 SEWER "F" RISER W/22 NOT
 FOUND WITH OTHER RISERS. SUBMIT RISER.
 FIXTURE UNITS/PIPE SIZE NOT CORRECT AS
 INDICATED IN PREVIOUS REVIEW.
 SEWER "D" PIPE SIZE FOR
 4,970 S.F. REQUIRES 8" PIPE. 6" SHOWN.
 PIPE SIZE FOR 783 S.F. REQUIRES 4" PIPE
 ON THE HORIZONTAL. 3" SHOWN.
 PIPE SIZE FOR 778 S.F. REQUIRES 4" PIPE
 ON THE HORIZONTAL. 3" SHOWN.
 4) SHTS P-202 & P-405 - 6" HUB DRAIN
 SHOWN TO BOTH SANITARY AND TO STORM.
 DELETE FROM SANITARY SYSTEM ON BOTH
 SHEETS.
 5) SHT P-202 NO SANITARY TO LAV IN HDCP
 STALL MEN'S LOCKER ROOM.
 6) SHT P-203 OVERFLOW FROM THE COOLING
 TOWER SHALL DRAIN TO STORM. THE COOLING
 TOWER SHALL DRAIN TO SANITARY.
 7) PLANS HAVE NOT BEEN ROUTED TO THE
 PALM BEACH HEALTH UNIT. THIS SHALL BE
 DONE PRIOR TO ISSUING A PERMIT.
 8) SHTS A-2.14, A-2.42, & A-2.43 MANUF.
 INFORMATION REQUIRED FOR SHOWERS TO
 VERIFY COMPLIANCE WITH HEIGHT OF GRAB
 BARS PER FHA DESIGN MANUAL.
 9) SHT A-8.11 TOILET ROOM DOORS SHALL
 NOT OPEN INTO THE CLEAR FLOOR SPACE OF
 THE TURNING RADIUS. SEC 11-4.22.2
 10 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 ONLY WATER HEATER SHEETS SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692