Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-07-17 00:00:00 | *************** UNSAT *************** | | | | 1)NOTE: PLEASE SEE NOTES PREVIOUS REVIEW | | S. PLEASE SUBMIT MORE INFORMATION FOR | | FIRE PUMP. HP, CODE LETTER, VOLTAGE, | | FEED AND OCP FROM GENERATOR/ ATS, | | ETC. | | REPSONSE ADDED FEEDER SIZE AND NOTE FOR | | OCP TO BE SET FOR LOCKED ROTOR CURRENT. | | NONE OF THIS CAN BE VERIFIED DUE TO | | LACK OF INFORMATION. | | PLEASE PROVIDE THIS INFORMATION ON RISER | | DIAGRAM AND PLANS. SPECS FROM MANUF. | | MAY BE SUBMITTED TO HELP FOR REVIEW AND | | /OR ANY FIRE REVIEW COMMENTS/QUESTIONS. | | | | PLEASE SEE ATTACHED LETTER FOR FS. | | 553.80(2)(B) | | | | 2)NOTE: AS PER CONVERSATION WITH | | ENGINEER, THREE SIGNED, DATED AND SEALED | | LETTERS WERE GOING TO ACCOMPANY PLANS | | THAT VERIFY ALL CONTINUOUS LOADS ARE | | AT 125%.215-3,230-42 ETC. | | PLEASE NOTE, THIS WAS NOT SUIBMITTED AND | | PLANS HAVE NOT BEEN REVISED OR NOTE | | THIS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|