Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop E
Sequence Number 4
Notes
Date Text
2003-07-17 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES PREVIOUS REVIEW
 S. PLEASE SUBMIT MORE INFORMATION FOR
 FIRE PUMP. HP, CODE LETTER, VOLTAGE,
 FEED AND OCP FROM GENERATOR/ ATS,
 ETC.
 REPSONSE ADDED FEEDER SIZE AND NOTE FOR
 OCP TO BE SET FOR LOCKED ROTOR CURRENT.
 NONE OF THIS CAN BE VERIFIED DUE TO
 LACK OF INFORMATION.
 PLEASE PROVIDE THIS INFORMATION ON RISER
 DIAGRAM AND PLANS. SPECS FROM MANUF.
 MAY BE SUBMITTED TO HELP FOR REVIEW AND
 /OR ANY FIRE REVIEW COMMENTS/QUESTIONS.
  
 PLEASE SEE ATTACHED LETTER FOR FS.
 553.80(2)(B)
  
 2)NOTE: AS PER CONVERSATION WITH
 ENGINEER, THREE SIGNED, DATED AND SEALED
 LETTERS WERE GOING TO ACCOMPANY PLANS
 THAT VERIFY ALL CONTINUOUS LOADS ARE
 AT 125%.215-3,230-42 ETC.
 PLEASE NOTE, THIS WAS NOT SUIBMITTED AND
 PLANS HAVE NOT BEEN REVISED OR NOTE
 THIS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW