Date |
Text |
2003-07-14 00:00:00 | PLEASE SEPARATE THE PLANS INTO SEPARATE |
| MANAGEABLE GROUPS.THE LARGE ROLL OF |
| LOOSE PAGES IS UNACCEPTABLE. COLLATE |
| THE MOST RECENT PLANS PAGES THAT ARE TO |
| BE PERMITTED INTO ARCHITECTURAL, MEP, |
| AND ANCILLARY AREAS SUCH AS FOOD |
| EQUIPMENT, LANDSCAPE, IRRIGATION, ETC. |
| ALSO, REVISE THE INDEX PAGE(S) TO |
| REFLECT THE DRAWINGS IN THE SET. THREE |
| COMPLETE SETS OF ALL PERTINENT |
| INFORMATION, SUCH AS PRODUCT APPROVALS, |
| TEST REPORTS, ETC. WILL BE NECESSARY. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED A THRESHOLD INSPECTION PLAN MUST |
| BE PROVIDED TO THE CITY. SEE FBC 105.13 |
| |
| BEFORE A PERMIT MAY BE ISSUED IMPACT |
| FEES MUST BE PAID TO THE COUNTY, THE |
| PERMIT PLANS STAMPED BY THAT OFFICE AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO |
| THE PERMIT APPLICATION. CALL |
| 561-233-5025 FOR MORE INFORMATION. |
| |
| SHEET S2.19, PLEASE CLARIFY THE |
| CONFLICTING COMPONENT AND CLADDING |
| PRESSURES WITH THE WINDOWS AND DOORS. |
| THE WIND LOAD SCHEDULE HAS A DIFFERENT |
| SET OF FIGURES AND CORNER DISTANCE THAN |
| WINDOW/DOOR WIND PRESSURE TABLE. |