Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop B
Sequence Number 4
Notes
Date Text
2003-07-14 00:00:00PLEASE SEPARATE THE PLANS INTO SEPARATE
 MANAGEABLE GROUPS.THE LARGE ROLL OF
 LOOSE PAGES IS UNACCEPTABLE. COLLATE
 THE MOST RECENT PLANS PAGES THAT ARE TO
 BE PERMITTED INTO ARCHITECTURAL, MEP,
 AND ANCILLARY AREAS SUCH AS FOOD
 EQUIPMENT, LANDSCAPE, IRRIGATION, ETC.
 ALSO, REVISE THE INDEX PAGE(S) TO
 REFLECT THE DRAWINGS IN THE SET. THREE
 COMPLETE SETS OF ALL PERTINENT
 INFORMATION, SUCH AS PRODUCT APPROVALS,
 TEST REPORTS, ETC. WILL BE NECESSARY.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED A THRESHOLD INSPECTION PLAN MUST
 BE PROVIDED TO THE CITY. SEE FBC 105.13
  
 BEFORE A PERMIT MAY BE ISSUED IMPACT
 FEES MUST BE PAID TO THE COUNTY, THE
 PERMIT PLANS STAMPED BY THAT OFFICE AND
 A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION. CALL
 561-233-5025 FOR MORE INFORMATION.
  
 SHEET S2.19, PLEASE CLARIFY THE
 CONFLICTING COMPONENT AND CLADDING
 PRESSURES WITH THE WINDOWS AND DOORS.
 THE WIND LOAD SCHEDULE HAS A DIFFERENT
 SET OF FIGURES AND CORNER DISTANCE THAN
 WINDOW/DOOR WIND PRESSURE TABLE.