2004-04-12 00:00:00 | PRODUCT APPROVAL SUBMITTAL |
| ***CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE NOA IS NO LONGER IN THE |
| PACKAGE THAT WAS PREVIOUSLY SUBMITTED |
| FOR THE MECHANICAL ROOF.ARE YOU USING |
| THE GUTTER ROOF PRODUCT AT THE |
| MECHANICAL ROOF?IT IS MARKED GUTTER |
| ROOF. |
| |
| 2.)A REQUEST WAS MADE FOR THE ORIGINAL |
| SIGNED AND SEALED COVER LETTER AND TEST |
| REPORT, SEE PREVIOUS LIST #3.THIS |
| IS NO LONGER IN THE PACKAGE, ONLY |
| PRODUCT DATA. |
| |
| 3.)REGARDING SERIES 35H (MD) |
| STOREFRONT DOOR, STEELCRAFT DOORS, |
| SERIES 800 SERVICE DOOR, SERIES 2000 SGD |
| THE ZONE 5 PRESSURES EXCEED PRODUCT |
| LIMITATIONS.ARE THESE TO BE INSTALLED |
| IN ZONE 4 ONLY?WHAT WILL BE USED IN |
| ZONE 5? |
| |
| 4.)THE STEELCRAFT DOOR IS TO BE |
| TESTED TO ASTM E330-84, FBC35.PROVIDE |
| A SITE SPECIFIC OR SUBMIT A TEST REPORT |
| THAT COMPLIES WITH FBC.ALSO SEE |
| PREVIOUS NOTE IN REGARDS TO THE |
| PRESSURES. |
| |
| CC:DON NEELY |
2004-03-23 00:00:00 | ****CORRECTIONS**** |
| PRODUCT APPROVAL SUBMITTAL |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)NOA 030421.04, SIX STORY GUTTER |
| ROOFS - MAX DESIGN PRESSURE IS 97.5, |
| DESIGN PRESSURE FOR SIX STORY ROOF |
| IS 146.2.SEE GENERAL LIMITATION #9. |
| |
| 2.)NOA 030212.06, THREE STORY |
| MECHANICAL ROOF - MAX DESIGN PRESSURE IS |
| -75, DESIGN PRESSURE FOR THREE STORY IN |
| ZONE 2 IS 88.3.ENHANCED FASTENING, |
| RATIONAL ANALYSIS OR EXTRAPOLATION |
| IS TO BE DONE BY THE DESIGNER OF |
| RECORD.SEE GENERAL LIMITATION #7. |
| |
| 3.)JOHNS MANVILLE MODIFIED BITUMEN |
| TEST REPORT - SUPPLY AN ORIGINAL |
| SIGNED AND SEALED COVER LETTER FROM |
| ATLANTIC CARRIBEAN. (FOR ONE AND THREE |
| STORY ROOFS) |
| |
| THE FOLLOWING ROOF PRODUCT APPROVAL |
| SUBMITTALS ARE APPROVED CONDITIONALLY |
| SUBJECT TO REVIEW BY DESIGNERS OF |
| RECORD AS PER COMMENT ON MODIFIED |
| BITUMEN ROOFING SHOP DRAWINGS: |
| ULTRAGUARD PVC-LIGHTWEIGHT CONCRETE DE |
| BASE SHEET ATTACHMENT CALCS, 1 STORY |
| BASE SHEET ATTACHMENT CALCS, 3 STORY |
| ALTUSA S |
| POLYFOAM |
| TILE SPECS, SYSTEM B |
| TILE UNDERLAYMENT FASTENER SPACING |
| TILE ATTACHMENT CALCS |
| |
| 4.)AS PER CONVERSATION WITH BOB |
| LUTHER, WINDOW DESIGN PRESSURES WERE |
| NOT ON THE PLAN AND WERE PROVIDED AS |
| A SEPARATE SUBMITTAL.PROVIDE A COPY |
| FROM THE ENGINEER SO THAT THE OTHER |
| PRODUCTS SUBMITTED CAN BE REVIEWED. |
| |
| |
| ROOF SUBMITTAL #07A-05-07552-0 |
| SIX STORY MODIFIED ROOF DATA |
| |
| ROOF SUBMITTAL #07A-04-07522-0 |
| 1 & 3 STORY MODIFIED ROOF DATA |
| |
| PLEASE RESUBMIT AFTER APPROVAL OF |
| SYSTEM (TEST REPORTS) BY DESIGNER OF |
| RECORD. |
| |
| |
| |
| |
| |
| CC:DON NEELY |