2003-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FHA-AMEND 98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW: SUBMIT CALCUL-
 ATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS. INCLUDE 1/2 AREA OF ALL VERTICAL
 WALLS, (INCLUDING PARAPETS), AND AREA OF
 ROOFS THAT DRAIN DOWN FROM ABOVE. EACH
 AREA IS AFFECTED BY VERTICAL WALLS, AND
 SOME ARE AFFECTED BY ADDITIONAL AREA OF
 ROOF THAT DRAIN FROM ABOVE, I.E. STAIR
 ROOFS, MECHANICAL ROOM ROOFS, ECT.
 PLEASE CALCULATE EACH AREA WITH ALL IN-
 FORMATION REQUESTED INCLUDED. ALSO IN-
 DICATE HOW INTERNAL AREAS OF THE ROOF,
 (WITH OUT SCUPPERS), IMPACT AREAS AROUND
 THEM AS FAR AS SIZING SCUPPERS. SHOW
 CALCULATIONS FOR SIZING SCUPPERS IN
 SURROUNDING AREAS. 1106/107
 2) SHTS P-407, & P408 STORM WATER RISER
 ISOMETRIC. SOME PIPE SIZING IS NOT CORR-
 ECT. PIPE SIZED FOR VERTICAL RISER, BUT
 HAS HORIZONTAL OFFSET THAT NEED TO BE
 SIZED FOR HORIZONTAL. (SEE RED LINE
 COMMENTS ON SHEETS). ALSO SEE PREVIOUS
 COMMENT PRIOR TO ADJUSTING PIPE SIZE.
 TABLE 1106.3
 3) SHTS P409, & P410 SANITARY RISER DIA-
 GRAM DOES NOT REFLECT THE FLOOR PLAN.
 SOME PIPING IS NOT SIZED CORRECTLY.
 SOME CLEANOUTS NOT SHOWN. RECHECK THE
 FIXTURE UNIT ADDITION. TABLE 710.1(1)
 4) SHT P-202 STORM WATER PIPING DOES NOT
 MATCH LEGEND SHT P-101. 104.2.1
 5) SHT P-202 PLEASE INDICATE WHAT WILL
 BE DRAINING INTO 6" H.D. IN POOL/MECH.
 ROOM #C161. (POOL DRAIN/OVERFLOW TO STOR
 M, AND WASTE FROM POOL TO SANITARY.)
 SEC 104.2.1
 6) SHT P-201 INDICATE TYPE OF BUSINESS
 IN BISTRO SERVERY. WILL FOOD BE PREPARED
 OR SERVED?SEC 104.2.1
 7) SHT P-201 MENS TOILET ROOM, (C166), &
 WOMENS TOILET ROOM, (C165). NO SANITARY
 PIPING SHOWN FOR LAVS IN HDCP STALLS.
 SECTION 104.2.1
 8) SHT P-409 BLDG. DRAIN ISOMETRIC,
 SHOWS BLDG. DRAIN "B" DRAINING INTO BLDG
 DRAIN "D", FUT FLOOR PLAN SHT P-202
 SHOWS "B" DRAINING TO "F". PLEASE CLAIR-
 FY.SEC 104.2.1
 9) SHT P-203 NO SANITARY DRAINAGE PIPING
 TO ICE BIN #130, AND WORK COUNTER SINK
 #129. PLEASE CLAIRFY. SEC 104.2.1
 10) SHT P-410 BLDG DRAIN ISO "G" IS NOT
 COMPLETE. MISSING RISERS B/49, B/57,
 B/51, B/52, KS/32, & KS/33. SEC 104.2.1
 11) SHTS P-410, P-202, & P-203,CLEANOUTS
 REQUIRED PER SECTION 708.3.3. PLEASE
 SHOW ON FLOOR PLAN AND ISOMETRIC.
 12) SHTS P-409 & P-410, COMPLETE RISER
 REQUIRED FOR 1ST FLOOR BLDG DRAIN. FOR
 AN EXAMPLE BLDG DRAIN "H" SHOW ALL FIX-
 TURES ON RISER DIAGRAM. SOME AREAS JUST
 HAVE A LINE WITH FIXTURE UNITS BUT DO
 NOT SHOW FIXTURES.SEC 104.2.1
 13) SHT P-203 PLEASE INDICATE WHAT WILL
 BE DRAINED INTO 4" H.D. IN COOLING TOWER
 ENCLOSURE.SEC 104.2.1
 14) SHT P-402 SANITARY RISER DIAGRAM
 #B/9 DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CLAIRFY.SEC 104.2.1
 15) SHT P-403 RISERS B/17 & B/18 START
 ON 1ST FLOOR SHT P-201, BUT DO NOT SHOW
 UP ON SHT P-207, (B/17), SHT P-210, BOTH
 SHT P-213, BOTH, AND SHT P-215, BOTH.
 PLEASE CLAIRFY. SEC 104.2.1
 16) SHT P-406 SANT RISER B/19 SHOWN ON
 1ST FLOOR OF SHT P-201 & P-207, BUT NOT
 FOUND ON SHTS P-210, P-213, P-215, OR
 P-217. FLOOR PLAN DOES NOT REFLECT THIS
 RISER OR THE FIXTURES CALLED FOR ON THE
 RESER. ALSO THERE IS ONLY A W/C SHOWN ON
 THE THIRD FLOOR OF RISER. SEC 104.2.1
 17) SHT P-406 RISER B/29 MISSING VENT
 FOR 2ND FLOOR. SEC 104.2.1
 18) SHT P-409 BLDG DRAIN ISOMETRIC DOES
 NOT REFLECT THE FLOOR PLAN. ISO SHOWS
 RISER W/10, AND FLOOR PLAN SHOWS B/19.
 PLEASE CLAIRFY.SEC 104.2.1
 THE FOLLOWING ITEMS HAVE NOT BEEN
 ADDRESSED. SEE ATTACHES SHEET REFERENC-
 ING FLORIDA STATUTE 553.80(2)(B). THIS
 WAS THE THIRD REVIEW.
 19) PLANS SHALL BE ROUTED TO THE PLAM
 BEACH HEALTH UNIT. THIS SHALL BE DONE
 PRIOR TO RESUBMITTING TO THE CITY FOR
 REVIEW.SEC 101.4.7
 20) SHTS A-2.41, A-2.42, & A-2.43. NO
 MEASURMENTS FOR BACKING SHOWN ON PLANS.
 (FHA DESIGN MANUAL REQUIREMENT #6)
 SPECIFICATION "A" OR "B" HAS NOT BEEN
 INDICATED. (FHA DESIGN MANUAL REQUIRE-
 MENT 7B). W/C OPENINGS NOT SHOWN. (FHA
 DISIGN MANUAL 7B. SEC 104.2.1
 21) SHT A-8.11 TURNING CIRCLE NOT SHOWN
 FOR PUBLIC AND COMMON USE TOILET/BATHING
 ROOMS. 11-4.22.3SEC 104.2.1
 22) SHT A-8.13 ELEVETIONS 8B, 8C, & 8D
 DO NOT MATCH INDICATOR ON DETAIL #1 SHT
 A-2.41SEC 104.2.1
 23) THE PERSONAL SEAL, SIGNATURE AND THE
 DATE OF THE ARCHITECT SHALL APPEAR ON
 ALL ARCHITECTURAL DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD. NO DATES APPEAR ON
 THE SEAL.61G1-16.003
 24) SUBMIT MANUF SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH THE
 FBC-2001 FUEL GAS CODE SEC 402.2. THE
 WATER HEATER HEATER SHEETS WERE SUBMITT-
 ED, BUT NOT THE REST OF THE EQUIPMENT.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692