Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop E
Sequence Number 3
Notes
Date Text
2003-05-21 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT ADDITIONAL
 INFORMATION FOR FIRE PUMP. SIZE (HP),
 FEEDERS, ETC. PLEASE NOTE ON PLANS
 FOR OCP TO BE SET FOR LOCKED ROTOR
 CURRENT. 695-4-B-1. PLEASE ALSO NOTE/
 CLARIFY MEANS OF DISCONNECT, RATED FOR
 LOAD , MANUAL. 230-76, 230-79.
  
  
 PLEASE NOTE, THE ABOVE SEEMS TO BE THE
 ONLY OUTSTANDING ISSUE.
 SPOKE TO ENGINEER ON 5/21/2003 AND HE
 TRY TO GET INFORMATION.
 PLEASE PROVIDE 3- SIGNED AND SEALED
 LETTERS FROM ENGINEER THAT VERIFIES ALL
 CONTINUOUS LOAD S ARE AT 125%.
 215-3,230-42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  