Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-05-20 00:00:00 | SHEET 5/S2.17 STILL CALLS OUT PLYWOOD | | SHEATHING ALTHOUGH THE GRAPHIC | | DEPICTION IS NOW METAL DECKING.PLEASE | | REVISE AS NECESSARY. | | | | SHEET S-2.24 CALLS FOR A 8000 PSI | | CONCRETE PUDDLING AT SELECTED COLUMN | | LOCATIONS AS TYPICAL.THESE 8000 PSI | | AREAS DONOT HAVE DIMENSIONS ORA | | DIRECTIONS FOR THE TRANSITION TO THE | | 5000 PSI CONCRETE IN THE REMAINDER OF | | THE FLOOR SLAB.PLEASE PROVIDE NOTES | | ON THE PLAN AS NECESSARY. | | | | THE SBCCI REPORT #9964 IS NOT CURRENTLY | | LISTED.PLEASE PROVIDE A CURRENT REPORT | | AND VERIFY THE DESIGN PRESSURES WITH | | THOSE ON THE PLANS. | | | | THE NOA FOR THE ROOF TILES #02-1115.03 | | IS LIMITED TO WOOD DECK APPLICATIONS. | | PROVIDE A COMPATIBLE SYSTEM. | | | | PLEASE PROVIDE A THRESHOLD INSPECTION | | PLAN. | | | | THE NOTICE OF COMMENCEMENT PROVIDED HAS | | NOT BEEN RECORDED WITH THE CLERK OF THE | | COURTS. | | | | IMPACT FEES MUST BE PAID TO THE COUNTY | | PRIOR TO PERMIT ISSUE. |
|