2003-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FBC-2001 FHA-98 DESIGN MANUAL
  
 1) MOST OF THE FOLLOWING COMMENTS WERE
 FROM THE PREVIOUS PLAN REVIEW AND WERE
 NOT ADDRESSED.
 2) PLANS SHALL BE ROUTED TO THE PALM
 BEACH HEALTH UNIT.
 3) GREASE TRAP SHALL BE SIZED BY UTILITY
 DEPT. CONTACT R. COMPO (561) 837-4074.
 4) SHT A-2.31 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. IN-
 CLUDE 1/2 AREA OF ALL VERTICAL WALLS,
 AND AREA OF ROOFS DRAINING ON TO ROOF
 FROM ABOVE.
 5) SUBMIT A HORIZONTAL STORM BLDG DRAIN.
 SHOW ALL RISERS AS THEY TIE INTO STORM
 DRAIN AS SHOW SQUARE FOOTAGE AS IT ACCU-
 MULATES IN SYSTEM.
 6) SHTS A-2.41, A-2.42, & A-2.43, NO
 MEASUREMENTS FOR BACKING SHOWN ON PLANS.
 SPECIFICATION "A" OR "B" ARE NOT SHOWN
 AS REQUIRED IN REQ. #7. W/C OPENING NOT
 SHOWN AS REQUESTED.
 7) SHT A-8.11 TURNING CIRCLE NOT SHOWN
 IN EACH TOILET ROOM AS REQUIRED.
 8) SHT A-8.13 ELEVATIONS 8B, 8C, & 8D DO
 NOT MATCH INDICATOR ON DETAIL #1 SHT.
 A-2.41
 9) SHT P-102 WATER HEATER "A" DETAIL,
 COMBUSTION AIR INTAKE SHALL BE SIZED AND
 INSTALLED PER MANUF. INSTALL. INSTRUCTS.
 PROVIDE INFORMATION FOR REVIEW.
 10) SHTS P-103 & P-404 WATER RISERS,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN EFFECTIVE RANGE,
 NOT IN CEILING. PER PDI-WH 201 AND MANUF
 INSTALL. INSTRUCTIONS.
 11) SHTS P-103, P-202, & P-404, VENTS
 ARE REQUIRED FOR SHOWERS IN MENS & WO-
 MENS LOCKER ROOMS.
 12) SHT P-201 SANITARY DRAINAGE PIPE
 (BURIED) DOES NOT MATCH LEDGEND ON SHT
 P-101. (ALSO SHT P-202)
 13) SHT P-202 CLEAN OUTS REQUIRED IN
 SANITARY BLDG. DRAIN. MAX. 100'.
 14) SUBMIT A SANITARY BLDG DRAIN. SHOW
 PIPE SIZES, CLEANOUTS, RISERS, AND SHOW
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 BLDG DRAIN.
 15) SHT P-202 ITEM P-145 FILTER TO BE
 NSF APPROVED. PROVIDE MANUF. INFORMATION
 16) SHTS P-202/P-203, ITEMS P-125, AND
 P-124, FUNNEL DRAINS NOT APPROVED. ALL
 INDIRECT WASTE SHALL DRAIN INTO FLOOR
 SINKS. SEC 802.3
 17) SHT P-207 STACK B/19 NOT FOUND.
 PLEASE CLAIRFY. ROOM C220
 18) SHT P-207 STACK KS/9 IN MIDDLE OF
 ROOM? NO WATER TO KITCHEN SINK. RM C220
 19) SHTS P-216 & P-218, SIZE WATER MAINS
 OVERHEAD IN CORRIDOR.
 20) SHT P-301 SHOW PIPE SIZES FOR RISER
 "A".
 21) SHT P-401 SHOW PIPE SIZES FOR WATER
 MAINS IN KITCHEN CEILING.
 22) SHT P-405 BTU LOAD OF GAS APPLIANCES
 SHOWS 5,189,000 ON PLANS BUT ONLY ADDS
 UP TO 4,266,000. PLEASE CLAIRFY.
 23) SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SECTION
 304. SUBMIT MANUF. INFO. FOR COMBUSTION
 AIR DIRECT VENT.
 24) SUBMIT MANUF. SHEET FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, AND THE FBC-2001 FUEL
 GAS CODE SEC 402.2
 25) EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 26) SHT P-402 SANT. RISERS B/4, B/5, B/6
 B/8, B/9, & KS/2 - VENT SHALL NOT TIE
 BACK INTO WASTE STACK AS SHOWN.
 27) SHTS P-402, & P-403 ALL VENT STACKS
 SHALL BE WASHED AT THE BASE. START ALL
 VENT STACKS FROM THE LOWEST FIXTURE
 GROUP.
 28) SHT P-403 RISERS B/15, B/16, & B/18
 VENT SHALL NOT TIE BACK INTO WASTE STACK
 AS SHOWN.
  
 WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377 OR805-6721
 FAX 653-2692