2003-04-11 00:00:00 | 1.PLAN SHEET M-102 NOTE #4, "SEE |
| M-200" THIS SHEET WAS NOT SUBMITTED. |
| NOTE #6 "SEE DIVISION 16 SERIES DWG", |
| PLEASE CLARIFY. |
| |
| 2.PLAN SHEET M-101, ATRIUM SMOKE |
| CONTROL - CODE SECTION 403.6.6.1, SHOULD |
| THIS READ 414.4.2. |
| |
| 3.PLAN SHEET M-202, PLAN NOTE #4 |
| "RANGE HOOD BY OTHERS" - SEPARATE PLANS |
| AND PERMITS REQUIRED FOR HOOD, FIRE |
| SUPPRESSION AND WALK-IN COOLERS. |
| |
| 4.PLAN SHEET M-203, HOOD CONNECTION |
| TRANSITION DUCTWORK COMMENTS 1,2,& 11, |
| INDICATE GREASE DUCT CLEARANCE TO |
| COMBUSTIBLES, WILL DUCT BE IN A SHAFT, |
| OR WILL FIREWRAP BE USED? |
| |
| 5.M-203, DUCT PENETRATIONS INTO AHU |
| ROOM A135 NO FIRE DAMPERS INDICATED. |
| |
| 6.MULTIPLE FLOORS HAVE "STORAGE & |
| ELECTRICAL" ROOMS THAT HAVE A 1 HOUR |
| FIRE RESISTANCE RATING.THE MECHANICAL |
| PLANS CALL FOR UNDERCUT DOOR FOR AIR |
| MAKE UP.PLEASE CLARIFY HOW THE RATING |
| IS MET WITH THE DOOR UNDERCUT. |
| |
| 7.PLEASE NOTE, DEVELOPED LENGTH FOR |
| DRYER DUCTS SHALL NOT EXCEED 25 FT. WITH |
| A 5 FT REDUCTION FOR EACH 90 DEGREE |
| RADIUS AND A 2 1/2 FT. REDUCTION FOR |
| EACH 45 DEGREE RAD. |
| |
| PROVIDE TEST CRITERIA FOR THE SMOKE |
| CONTROL. |
| |