2003-04-24 00:00:00 | 1) AL DINING ROOM A128,A128B, DISPLAYS |
| ONLY ONE EXIT SIGN. |
| |
| 2) IS THE DOOR SWING SHOWN IN DINING |
| ROOM AREA A, SWINGING IN THE RIGHT |
| DIRECTION. |
| |
| 3) EXIT SIGN IN MULTI-USE FOYER C156 |
| LEADS WHERE. |
| |
| 4) VERANDA'S REQUIRED TO BE FIRE |
| SPRINKLER PROTECTED IF COMBUSTIBLE |
| CONSTRUCTION OR COMBUSTIBLES ARE |
| HANDLED OR STORED. |
| |
| 5) CORRIDOR A301 NEEDS EXIT SIGN AT |
| HALLWAY INTERSECTION. |
| |
| 6) PLEASE INDICATE TRAVEL DISTANCES |
| ON FLOORS 4,5,AND 6. |
| |
| 7) PLEASE INDICATE WHICH ELEVATORS ARE |
| STRETCHER ACCESSIBLE. |
| |
| 8) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| WON-DOORS. |
| |
| 9) WHAT PREVENTS PERSONS FROM SLIPPING |
| ON THE MARBLE TREADS ON THE GRAND STAIR. |
| |
| 10) PLEASE DISPLAY THE RESISTANT TO THE |
| PASSAGE OF A 4" SPHERE ON HANDRAILS. |
| |
| 11) PLEASE DISPLAY AISLES IN DINING |
| ROOMS 177A AND 177B. |
| |
| 12) THE LOCATION OF FIREFIGHTERS SMOKE |
| CONTROL ATRIUM PANEL SHOULD BE LOCATED |
| WHERE ALL OTHER LS SYSTEM PANELS ARE |
| LOCATED. |
| |
| 13) PLEASE PROVIDE TESTING REQUIREMENTS |
| AND A SEQUENCE OF OPERATION FOR ATRIUM |
| SMOKE CONTROL. |
| |
| 14) FP SCHEDULE AND NOTES BELOW IT DO |
| NOT CORRESPOND. |
| |
| 15) PLEASE EXPLAIN WHY POOL AREA IS NOT |
| FIRE SPRINKLER PROTECTED. |
| |
| 16) HOW ARE TWO STANDPIPES SHOWN ON |
| PLANS 4-6TH FLOORS ABLE TO COVER ALL |
| AREAS OF THE BUILDING. |
| |
| 17) PLEASE INDICATE HOW SECURITY |
| FEATURES INSTALLED ON EXIT DOORS |
| WILL EFFECT EXITING. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |
| 835-2910 |