Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop E
Sequence Number 2
Notes
Date Text
2003-03-20 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS, THERE ARE
 STILL MANY RECEPTS MISSING PER 210-52
 PLEASE ALSO SEE KITCHEN COUNTERSPACE
 PER 210-52-C1
  
 2)NOTE: PLEASE SEE SOME UNITS HAVE MISS-
 -ING SD`S INSIDE BEDROOMS OR ARE MISSING
 OUTSIDE. NFPA-72
  
 3)NOTE: MDPL AND MDPHARE SHOWN W/ NO
 MAINS?? PLEASE SEE E-503, ONE ? AND
 AS MLO. PLEASE SEE 230-70/230-2/230-72
  
 4)NOTE: PLEASE SHOW SIZE OF DS-EQ AND
 DS-LS. IT IS NOTED BY ALL NOTES ON
 RISER DIAGRAM THAT ATS,EQ&LS MDP`S ARE
 ALL 400A.HOWEVER UPON REVIEW OF SEC`S
 FROM FPL, EQ HAS ONLY ONE SET OF 3/0`S
 WHICH ARE ONLY RATED FOR 200A'S?
 PLEASE CLARIFY SIZING OF DISC AND SEC`S
 PLEASE ALSO PROVIDE AIC RATINGS FOR BOTH
 MAINS. EQ HAS "NOTE 8" FOR GREEN AND
 LS DOES NOT HAVE "NOTE 1"?
  
 5)NOTE: PLEASE CLARIFY GFI PROTECTION
 PER 517-17. IT WAS NOTED THAT GFI
 PROTECTION IS NOTED FOR MDPH. NO MAIN?
  
 6)NOTE: PLEASE SEE NOTE ON ELECTRICAL
 LOAD CALCS. MENTIONS 1ST 10KW@100% AND
 REMAINDER AT 40% PER 220-13.
 PLEASE SEE 220-13,, REMAINDER IS NOT 40%
 NEC SHOWS 50%.
 PLEASE CLARIFY/SHOW LOAD CALC FOR MDPH.
 E-509 SHOWS MDPA?
  
 7)NOTE: PLEASE SUBMIT AND SHOW ALL
 CONTINUOUS LOADS AT 125%, 215-3,230-42
 ETC.
  
 8)NOTE: PLEASE SEE UNIT PANEL SCHEDULES.
 ONLY SHOW ONE SMALL APPL CIRCUIT?
 PLEASE SEE NEC 210-11-C1
  
 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES
 FOR APT UNIT. 210-12
  
 10)NOTE:PLEASE SEE "TYPICAL" LIST SHOWN
 FROM 4WDL, PANELS SHOWN AS "SL`S".
  
 11)NOTE: PLEASE SEE UNIT TYPE "S" PANEL
 SCHEDULE SHOWN. SHOWN AS BEING #224
 WHEN YO GO TO RISER DIAGRAM, #224 IS
 BEING FED FROM "2NDL" AND YET 2NDL PANEL
 SCHEDULE DOES NOT SHOW A TYPE "S"??
 PLEASE CORRELATE PANEL SCHEDULES FOR
 THIS AND OTHERS.
  
 12)NOTE: PLEASE SEE THAT ELECTRICAL
 ROOM FOR FIRE PUMP IS SHOWN,BUT NOTHING
 SHOWN ON RISER DIAGRAM FOR FIRE PUMP/
 OCP/AWG??? PLEASE ALSO NOTE ON PLANS
 OCP FOR FIRE PUMP PER 695-4B-1
 NOT ENOUGH INFORMATION IN SPECS FOR
 FIRE PUMP/OCP/SIZE/CODE LETTER ETC.
 PLEASE GO OVER PLANS AND REVISE.
 PLEASE NOTE DUE TO PLANS NOT BEING
 COMPLETE THE FIRST TIME THEY CAME IN.
 SOME OF THESE COMMENTS ARE NEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372