2003-03-20 00:00:00 | ************ UNSAT ***************** |
| |
| 1)NOTE: PLEASE SEE PLANS, THERE ARE |
| STILL MANY RECEPTS MISSING PER 210-52 |
| PLEASE ALSO SEE KITCHEN COUNTERSPACE |
| PER 210-52-C1 |
| |
| 2)NOTE: PLEASE SEE SOME UNITS HAVE MISS- |
| -ING SD`S INSIDE BEDROOMS OR ARE MISSING |
| OUTSIDE. NFPA-72 |
| |
| 3)NOTE: MDPL AND MDPHARE SHOWN W/ NO |
| MAINS?? PLEASE SEE E-503, ONE ? AND |
| AS MLO. PLEASE SEE 230-70/230-2/230-72 |
| |
| 4)NOTE: PLEASE SHOW SIZE OF DS-EQ AND |
| DS-LS. IT IS NOTED BY ALL NOTES ON |
| RISER DIAGRAM THAT ATS,EQ&LS MDP`S ARE |
| ALL 400A.HOWEVER UPON REVIEW OF SEC`S |
| FROM FPL, EQ HAS ONLY ONE SET OF 3/0`S |
| WHICH ARE ONLY RATED FOR 200A'S? |
| PLEASE CLARIFY SIZING OF DISC AND SEC`S |
| PLEASE ALSO PROVIDE AIC RATINGS FOR BOTH |
| MAINS. EQ HAS "NOTE 8" FOR GREEN AND |
| LS DOES NOT HAVE "NOTE 1"? |
| |
| 5)NOTE: PLEASE CLARIFY GFI PROTECTION |
| PER 517-17. IT WAS NOTED THAT GFI |
| PROTECTION IS NOTED FOR MDPH. NO MAIN? |
| |
| 6)NOTE: PLEASE SEE NOTE ON ELECTRICAL |
| LOAD CALCS. MENTIONS 1ST 10KW@100% AND |
| REMAINDER AT 40% PER 220-13. |
| PLEASE SEE 220-13,, REMAINDER IS NOT 40% |
| NEC SHOWS 50%. |
| PLEASE CLARIFY/SHOW LOAD CALC FOR MDPH. |
| E-509 SHOWS MDPA? |
| |
| 7)NOTE: PLEASE SUBMIT AND SHOW ALL |
| CONTINUOUS LOADS AT 125%, 215-3,230-42 |
| ETC. |
| |
| 8)NOTE: PLEASE SEE UNIT PANEL SCHEDULES. |
| ONLY SHOW ONE SMALL APPL CIRCUIT? |
| PLEASE SEE NEC 210-11-C1 |
| |
| 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS ON PANEL SCHEDULES |
| FOR APT UNIT. 210-12 |
| |
| 10)NOTE:PLEASE SEE "TYPICAL" LIST SHOWN |
| FROM 4WDL, PANELS SHOWN AS "SL`S". |
| |
| 11)NOTE: PLEASE SEE UNIT TYPE "S" PANEL |
| SCHEDULE SHOWN. SHOWN AS BEING #224 |
| WHEN YO GO TO RISER DIAGRAM, #224 IS |
| BEING FED FROM "2NDL" AND YET 2NDL PANEL |
| SCHEDULE DOES NOT SHOW A TYPE "S"?? |
| PLEASE CORRELATE PANEL SCHEDULES FOR |
| THIS AND OTHERS. |
| |
| 12)NOTE: PLEASE SEE THAT ELECTRICAL |
| ROOM FOR FIRE PUMP IS SHOWN,BUT NOTHING |
| SHOWN ON RISER DIAGRAM FOR FIRE PUMP/ |
| OCP/AWG??? PLEASE ALSO NOTE ON PLANS |
| OCP FOR FIRE PUMP PER 695-4B-1 |
| NOT ENOUGH INFORMATION IN SPECS FOR |
| FIRE PUMP/OCP/SIZE/CODE LETTER ETC. |
| PLEASE GO OVER PLANS AND REVISE. |
| PLEASE NOTE DUE TO PLANS NOT BEING |
| COMPLETE THE FIRST TIME THEY CAME IN. |
| SOME OF THESE COMMENTS ARE NEW. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |