Plan Review Notes For Permit 02060381 |
Permit Number |
02060381 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-03-31 00:00:00 | SHEET S2.17 DOES NOT SHOW THE METHOD OF | | ATTACHMENT FOR THE METAL DECKING. | | | | SECTION 5/S2.17 CALLS OUT PLYWOOD ROOF | | SHEATHING WHICH IS NOT PERMITTED IN | | TYPE II CONSTRUCTION.SEE FBC 604. | | | | WHAT ARE THE DIMENSIONS OF THE GROUT | | SLEEVE SHOWN IN SECTION 16/S2.18? | | | | SECTIONS 5/S2.18 AND 16/S2.18, HOW ARE | | THE TRUSSES ATTACHED TO THE BUILDING? | | | | SHEET S 2.19 CALLS OUT EDGE/CORNER | | DISTANCES AS 10' AND 15', PLEASE | | CLARIFY. | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED IMPACT FEES MUST BE PAID TO THE | | COUNTY, THE PERMIT PLANS STAMPED BY | | THAT OFFICE AND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. CALL 561-233-5025 FOR | | MORE INFORMATION. |
|