Date Text
2004-01-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS P207, P208, P217, & P218 ALL
 SHOW 2" CONDENSATE RISER WITH A 2" HUB
 DRAIN, BUT SHOW 3" PIPED TO THE HUB
 DRAIN. PLEASE CLAIRFY.
 2) SHT P-402 SANITARY RISERS B/9 & B/25
 JANITOR SINK HAS BEEN ADDED TO RISERS.
 PER SECTION 909.1, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUP SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 3) SHT P-407 SANITARY RISER B/50 TRAP
 REQUIRED ON FIXTURE T-1 (TUB) 1002.1
 4) SHT P-407WATER RISERS 'A' & 'B' NO
 CHANGES WERE NOTED BUT RISERS WERE
 CLOUDED. WATER RISER 'A' REQUIRES FULL
 OPEN VALVES PER 606.1(4) AS INDICATED ON
 STAMPED SET OF PLANS. ALSO WASH MACHINE
 REQUIRES WATER HAMMER ARRESTORS NEAR THE
 FIXTURE. 604.9
 5) INFORMATIONAL - SHTS P-103 AND P-410
 REQUIRE REVISIONS PER STAMPED SET OF
 PLANS.
  