2002-07-09 00:00:00DENIED:
 1. NO FIRE DAMPERS ARE SHOWN AT RATED
 WALLS. 2001 FBC(M) 607.6 THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF
 EACH FIRE DOOR, FIRE DAMPER, CEILING
 DAMPER AND SMOKE DAMPER SHALL BE SHOWN
 AND PROPERLY INDENTIFIED ON THE
 BUILDING PLANS BY THE DESIGNER.
  
 2. PROVIDE SHAFT DETAILS FOR EXHAUST
 RISERS.
  
 3. PROVIDE DETAILS ON DRYER DUCTS.
  
 4. SHOW SEQUENCE OF OPERATION FOR ATRIUM
 SMOKE EVAC AND CALCULATIONS OF AIR
 FLOW.
  
 5. CHILLER ROOM REFRIGERANT RELIEF PIPE
 TO COMPLY WITH 2001 FBC(M) 1105.9
 PUSH BUTTON SILENCE ON REFRIGERANT
 LEAK DETECTOR MODULE SHALL NOT BE
 AVAILABLE.
 HORN AND STROBE SHALL BE VISIBLE AND
 AUDIBLE THOUGHOUT ENTIRE ROOM WITH
 EQUIPMENT RUNNING.
 SIGN IN NOTE 22 TO BE BY EVERY DOOR
 INTO CHILLER ROOM.
 BREATHING APPERATUS TO BE CLOSE TO
 MAIN ACCESS DOOR.
 SET POINT FOR ALARM AND EMERGENCY
 VENTILATION SHALL BE MINIMUM 1000PPM
 PER TABLE 1103.1
 IS THE REFRIGERANT PURGE EXHAUST
 FAN TO RUN CONTINUOUSLY?
  
 6. SEE 2001 FBC(M) 1206.1.1 FOR
 PROHIBITED TEE APPLICATIONS. "FLUID IN
 THE SUPPLY SIDE OF A HYDRONIC SYSTEM
 SHALL NOT ENTER A TEE FITTING THROUGH
 THE BRANCH OPENING."
  
 7. FLORIDA ENERGY CODE REQUIRES MINIMUM
 IPLV NOT SHOWN AS NPLV. PLEASE PROVIDE
 IPLV SHOWING COMPLIANCE WITH TABLE 4-5
  
 8. ROOF MOUNTED EQUIPMENT SUPPORTS
 HEIGHT IS BASED ON EQUIPMENT WIDTH PER
 TABLE 1511.7 2001 FBC.
  
 9. THE PLANS PROVIDED ARE NOT A COMPLETE
 SET AND FOLLOWING REVIEWS COULD REFLECT
 COMMENTS ON ITEMS NOT APPARENT UNDER
 THIS INCOMPLETE PLAN SET.
 PLANS ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGNER.