2002-07-09 00:00:00 | DENIED: |
| 1. NO FIRE DAMPERS ARE SHOWN AT RATED |
| WALLS. 2001 FBC(M) 607.6 THE SPECIFIC |
| LOCATION AND INSTALLATION DETAILS OF |
| EACH FIRE DOOR, FIRE DAMPER, CEILING |
| DAMPER AND SMOKE DAMPER SHALL BE SHOWN |
| AND PROPERLY INDENTIFIED ON THE |
| BUILDING PLANS BY THE DESIGNER. |
| |
| 2. PROVIDE SHAFT DETAILS FOR EXHAUST |
| RISERS. |
| |
| 3. PROVIDE DETAILS ON DRYER DUCTS. |
| |
| 4. SHOW SEQUENCE OF OPERATION FOR ATRIUM |
| SMOKE EVAC AND CALCULATIONS OF AIR |
| FLOW. |
| |
| 5. CHILLER ROOM REFRIGERANT RELIEF PIPE |
| TO COMPLY WITH 2001 FBC(M) 1105.9 |
| PUSH BUTTON SILENCE ON REFRIGERANT |
| LEAK DETECTOR MODULE SHALL NOT BE |
| AVAILABLE. |
| HORN AND STROBE SHALL BE VISIBLE AND |
| AUDIBLE THOUGHOUT ENTIRE ROOM WITH |
| EQUIPMENT RUNNING. |
| SIGN IN NOTE 22 TO BE BY EVERY DOOR |
| INTO CHILLER ROOM. |
| BREATHING APPERATUS TO BE CLOSE TO |
| MAIN ACCESS DOOR. |
| SET POINT FOR ALARM AND EMERGENCY |
| VENTILATION SHALL BE MINIMUM 1000PPM |
| PER TABLE 1103.1 |
| IS THE REFRIGERANT PURGE EXHAUST |
| FAN TO RUN CONTINUOUSLY? |
| |
| 6. SEE 2001 FBC(M) 1206.1.1 FOR |
| PROHIBITED TEE APPLICATIONS. "FLUID IN |
| THE SUPPLY SIDE OF A HYDRONIC SYSTEM |
| SHALL NOT ENTER A TEE FITTING THROUGH |
| THE BRANCH OPENING." |
| |
| 7. FLORIDA ENERGY CODE REQUIRES MINIMUM |
| IPLV NOT SHOWN AS NPLV. PLEASE PROVIDE |
| IPLV SHOWING COMPLIANCE WITH TABLE 4-5 |
| |
| 8. ROOF MOUNTED EQUIPMENT SUPPORTS |
| HEIGHT IS BASED ON EQUIPMENT WIDTH PER |
| TABLE 1511.7 2001 FBC. |
| |
| 9. THE PLANS PROVIDED ARE NOT A COMPLETE |
| SET AND FOLLOWING REVIEWS COULD REFLECT |
| COMMENTS ON ITEMS NOT APPARENT UNDER |
| THIS INCOMPLETE PLAN SET. |
| PLANS ARE REQUIRED TO BE SIGNED AND |
| SEALED BY THE DESIGNER. |