Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-06-20 00:00:001) ANY NEW SECURITY GATES ARE TO BE
 PROPERLY PERMITTED. PROVISIONS ARE TO
 BE MADE FOR FIRE AND PARAMEDICAL
 ACCESS THRU THE GATES. IF THE GATES
 ARE ELECTRIC, PROVISIONS ARE TO BE MADE
 IN THE EVENT OF LOSS OF POWER.
  
 2) ALL INGRESS LANES ARE TO BE AT LEAST
 20 FEET IN CLEAR WIDTH.
  
 3) PLEASE INDENTIFY ON THE PLANS THE
 REQUIRED FIRE LANE LOCATIONS.
  
 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5) WILL THE GUARDHOUSE BE STAFFED FULL
 TIME OR PART TIME.
  
 6) SUITABLE FIRE HYDRANTS ARE TO BE
 PROVIDED FOR FIRE AND PARAMEDICAL
 EQUIPMENT DURING CONSTRUCTION.
  
 7) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED DURING CONSTRUCTION.
  
 8) IT APPEARS THAT ADDITIONAL FIRE
 HYDRANTS APPEAR TO BE NEEDED NEAR THE
 PROPOSED RESIDENTIAL BUILDING.
  
 9) VALVES TO FIRE HYDRANTS ARE TO BE
 NO FARTHER THAN FOUR FEET TO THEM.
  
 10) NEW FIRE HYDRANTS ARE TO BE PROVIDED
 WITH SEVEN AND HALF FEET CLEARANCE
 TO THE FRONT AND SIDES OF THEM.
 CLEARANCE OF AT LEAST FOUR FEET IS TO
 BE PROVIDED TO THE REAR OF THEM.
  
 11) TAMPER SWITCHES, CHAINS AND LOCKS
 ARE REQUIRED ON THE BACKFLOW DEVICES.
  
 12) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFOMATION FOR WALLS
 AND CEILINGS.
  
 13) KNOX-BOXES WILL BE REQUIRED FOR THE
 BUILDING.
  
 14) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALUMINUM RAIL SYSTEM.
  
 15) EIFS COPING TRIM NOTED ON THE PLANS.
 PLEASE PROVIDE FLAME SPREAD DETAILS.
  
 16) PLEASE PROVIDE TRAVEL DISTANCES,
 COMMON PATHS OF TRAVEL, DEAD-END
 CORRIDORS ON THE LIFE SAFETY PLANS.
  
 17) ALL SHAFTWAYS THAT PERSONS CAN
 ENTER MUST BE MARKED "SHAFTWAY" IN
 RED LETTERS ON A WHITE BACKGROUND.
  
 18) SIGNS REQUIRED IN STAIRWELLS
 INDICATING STAIR NUMBER, TERMINUS,
 FLOOR LEVEL, ETC.
  
 19) AUTOMATIC SLIDING DOOR ASSEMBLIES
 TO COMPLY WITH APPLICABLE FIRE CODE
 REQUIREMENTS.
  
 20) LOCKS ON EXIT DOORS SHALL NOT
 REQUIRE THE USE OF A KEY, TOOL,
 SPECIAL KNOWLEDGE OR EFFORT. IF
 PERMITTED, DELAYED EGRESS OR ACCESS
 CONTROLLED LOCKS WILL BE ALLOWED.
  
 21) PORTECOCHERS'S IF FIRE AND
 PARAMEDICAL EQUIPMENT ARE EXPECTED TO
 PASS UNDERNEATH MUST BE AT LEAST
 THIRTEEN FEET SIX INCHES HIGH.
  
 22) IS THE DOOR IN MEDICAL CLINIC C134
 NEAR MITZVAH STORAGE C115 SWINGING IN
 THE RIGHT DIRECTION.
  
 23) ELECTRICAL PAGES AND LIFE SAFETY
 PLANS DO NOT MATCH WITH REGARDS TO
 EXIT SIGN LOCATIONS.
  
 24) MORE DETAILS REQUIRED ON FIRE PUMP.
  
 25) MORE DETAILS REQUIRED ON EMERGENCY
 GENERATOR.
  
 26) ELEVATORS TO COMPLY WITH 61C-5.
  
 27) FIRE PROTECTION NOTES # 9 INDICATES
 SIX SPARE FIRE SPRINKLER HEADS WILL
 BE PROVIDED. SIX SPARE SPRINKLER HEADS
 ARE WHEN THREE HUNDRED FIRE SPRINKLERS
 OR LESS ARE USED.
  
 28) FIRE SPRINKLER PLANS ARE INCOMPLETE.
 PLEASE PROVIDE COMPLETE FIRE SPRINKLER
 PLANS. NO FIRE DEPARTMENT CONNECTION'S
 ARE SHOWN.
  
 29) FIRE STANDPIPE INFORMATION MISSING
 FROM PLANS. PLEASE PROVIDE STANDPIPE
 RISER DIAGRAMS.
  
 30) HOW WILL THE BUILDING BE LICENSED.
 WILL IT BE RESIDENTIAL APARTMENTS,
 ADULT CONGREGATE LIVING FACILITY. PLEASE
 ADVISE.
  
 31) VISIBLE FIRE ALARM DEVICES ARE
 REQUIRED WITHIN APARTMENTS DESIGNED FOR
 THE HEARING IMPAIRED.
  
 32) ASSEMBLY ROOMS SUBJECT TO AN
 OCCUPANCY OF 100 OR MORE PERSONS MUST
 BE PROVIDED WITH PANIC HARDWARE ON THE
 EXIT DOORS.
  
 33) PLEASE PROVIDE DETAILS ON SERVICE
 TYPE SHAFTS.
  
 34) FIRE HYDRANTS ARE TO BE LOCATED
 WITHIN 150 FEET OF FIRE DEPARTMENT
 CONNECTIONS.
  
 35) SEVERAL PAGES OF PLANS ARE NOT
 SIGNED AND SEALED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910