2002-06-20 00:00:00 | 1) ANY NEW SECURITY GATES ARE TO BE |
| PROPERLY PERMITTED. PROVISIONS ARE TO |
| BE MADE FOR FIRE AND PARAMEDICAL |
| ACCESS THRU THE GATES. IF THE GATES |
| ARE ELECTRIC, PROVISIONS ARE TO BE MADE |
| IN THE EVENT OF LOSS OF POWER. |
| |
| 2) ALL INGRESS LANES ARE TO BE AT LEAST |
| 20 FEET IN CLEAR WIDTH. |
| |
| 3) PLEASE INDENTIFY ON THE PLANS THE |
| REQUIRED FIRE LANE LOCATIONS. |
| |
| 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 5) WILL THE GUARDHOUSE BE STAFFED FULL |
| TIME OR PART TIME. |
| |
| 6) SUITABLE FIRE HYDRANTS ARE TO BE |
| PROVIDED FOR FIRE AND PARAMEDICAL |
| EQUIPMENT DURING CONSTRUCTION. |
| |
| 7) TEMPORARY STANDPIPE SYSTEMS ARE |
| REQUIRED DURING CONSTRUCTION. |
| |
| 8) IT APPEARS THAT ADDITIONAL FIRE |
| HYDRANTS APPEAR TO BE NEEDED NEAR THE |
| PROPOSED RESIDENTIAL BUILDING. |
| |
| 9) VALVES TO FIRE HYDRANTS ARE TO BE |
| NO FARTHER THAN FOUR FEET TO THEM. |
| |
| 10) NEW FIRE HYDRANTS ARE TO BE PROVIDED |
| WITH SEVEN AND HALF FEET CLEARANCE |
| TO THE FRONT AND SIDES OF THEM. |
| CLEARANCE OF AT LEAST FOUR FEET IS TO |
| BE PROVIDED TO THE REAR OF THEM. |
| |
| 11) TAMPER SWITCHES, CHAINS AND LOCKS |
| ARE REQUIRED ON THE BACKFLOW DEVICES. |
| |
| 12) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATION INFOMATION FOR WALLS |
| AND CEILINGS. |
| |
| 13) KNOX-BOXES WILL BE REQUIRED FOR THE |
| BUILDING. |
| |
| 14) PLEASE PROVIDE PRESCRIPTIVE CODE |
| REQUIREMENTS FOR ALUMINUM RAIL SYSTEM. |
| |
| 15) EIFS COPING TRIM NOTED ON THE PLANS. |
| PLEASE PROVIDE FLAME SPREAD DETAILS. |
| |
| 16) PLEASE PROVIDE TRAVEL DISTANCES, |
| COMMON PATHS OF TRAVEL, DEAD-END |
| CORRIDORS ON THE LIFE SAFETY PLANS. |
| |
| 17) ALL SHAFTWAYS THAT PERSONS CAN |
| ENTER MUST BE MARKED "SHAFTWAY" IN |
| RED LETTERS ON A WHITE BACKGROUND. |
| |
| 18) SIGNS REQUIRED IN STAIRWELLS |
| INDICATING STAIR NUMBER, TERMINUS, |
| FLOOR LEVEL, ETC. |
| |
| 19) AUTOMATIC SLIDING DOOR ASSEMBLIES |
| TO COMPLY WITH APPLICABLE FIRE CODE |
| REQUIREMENTS. |
| |
| 20) LOCKS ON EXIT DOORS SHALL NOT |
| REQUIRE THE USE OF A KEY, TOOL, |
| SPECIAL KNOWLEDGE OR EFFORT. IF |
| PERMITTED, DELAYED EGRESS OR ACCESS |
| CONTROLLED LOCKS WILL BE ALLOWED. |
| |
| 21) PORTECOCHERS'S IF FIRE AND |
| PARAMEDICAL EQUIPMENT ARE EXPECTED TO |
| PASS UNDERNEATH MUST BE AT LEAST |
| THIRTEEN FEET SIX INCHES HIGH. |
| |
| 22) IS THE DOOR IN MEDICAL CLINIC C134 |
| NEAR MITZVAH STORAGE C115 SWINGING IN |
| THE RIGHT DIRECTION. |
| |
| 23) ELECTRICAL PAGES AND LIFE SAFETY |
| PLANS DO NOT MATCH WITH REGARDS TO |
| EXIT SIGN LOCATIONS. |
| |
| 24) MORE DETAILS REQUIRED ON FIRE PUMP. |
| |
| 25) MORE DETAILS REQUIRED ON EMERGENCY |
| GENERATOR. |
| |
| 26) ELEVATORS TO COMPLY WITH 61C-5. |
| |
| 27) FIRE PROTECTION NOTES # 9 INDICATES |
| SIX SPARE FIRE SPRINKLER HEADS WILL |
| BE PROVIDED. SIX SPARE SPRINKLER HEADS |
| ARE WHEN THREE HUNDRED FIRE SPRINKLERS |
| OR LESS ARE USED. |
| |
| 28) FIRE SPRINKLER PLANS ARE INCOMPLETE. |
| PLEASE PROVIDE COMPLETE FIRE SPRINKLER |
| PLANS. NO FIRE DEPARTMENT CONNECTION'S |
| ARE SHOWN. |
| |
| 29) FIRE STANDPIPE INFORMATION MISSING |
| FROM PLANS. PLEASE PROVIDE STANDPIPE |
| RISER DIAGRAMS. |
| |
| 30) HOW WILL THE BUILDING BE LICENSED. |
| WILL IT BE RESIDENTIAL APARTMENTS, |
| ADULT CONGREGATE LIVING FACILITY. PLEASE |
| ADVISE. |
| |
| 31) VISIBLE FIRE ALARM DEVICES ARE |
| REQUIRED WITHIN APARTMENTS DESIGNED FOR |
| THE HEARING IMPAIRED. |
| |
| 32) ASSEMBLY ROOMS SUBJECT TO AN |
| OCCUPANCY OF 100 OR MORE PERSONS MUST |
| BE PROVIDED WITH PANIC HARDWARE ON THE |
| EXIT DOORS. |
| |
| 33) PLEASE PROVIDE DETAILS ON SERVICE |
| TYPE SHAFTS. |
| |
| 34) FIRE HYDRANTS ARE TO BE LOCATED |
| WITHIN 150 FEET OF FIRE DEPARTMENT |
| CONNECTIONS. |
| |
| 35) SEVERAL PAGES OF PLANS ARE NOT |
| SIGNED AND SEALED. |
| |