2002-07-12 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE SOME MISSING RECEPTS
 PER 210-52.
  
 2)NOTE: PLEASE NOTE THAT SOME ELECTRICAL
 PANELS ARE SHOWN IN BATHROOMS. PLEASE
 NOTE THIS IS NOT PERMITTED PER 240-24
  
 3)NOTE: PLEASE SEE 110-26/384-7 FOR
 INSTALLATION OF PANELS IN STORAGE AREAS.
 PLEASE HAVE DEDICATED ELECTRICAL SPACE
 SHOWN ON PLANS.
 PLEASE NOTE THIS INCLUDES ALL PANELS AS
 SHOWN IN STORAGE ROOMS.
  
 4)NOTE: PLEASE NOTE SOME MISSING RECEPTS
 PER 210-52H
  
 5)NOTE: PLEASENOTE LABELING OF EQUIP-
 -MENT FOR ELECTRICAL ROOM LAYOUT. PLEASE
 NOTE MORETHAN ONE PANEL/TRANS ALL BEING
 SHOWN AS "X"??.
  
 6)NOTE: PLEASE NOTE GROUNDING OF ALL
 TRANSFORMERS NEED TOMORE DETAILED?
 PER 250-30
  
 7)NOTE: PLEASE SHOW AMPERAGE DESIGNATION
 -S ON LINE DIAGRAM. PLEASE NOTE THAT IN
 ORDER TO VERIFY WIRE SIZES YOU WOULD
 HAVE TO TURN PAGES ABCK AND FORTH FOR
 EACH PANEL AND OR PIECE OF EQUIPMENT.
  
 8)NOTE: PLEASE SHOW TRANSFORMER INFORMA-
 TION ON LINE DIAGRAM ALSO.
  
 9)NOTE: PLEASE NOTE THAT E-206 NEEDS TO
 SHOW LAYOUT OF EQUIPMENT IN MAIN
 ELECTRICAL ROOM AND GENERATOR ROOM.
  
 10)NOTE: PLEASE SHOW HOW MDPL AND MDPH
 ARE BEING FED? FROM FPL?
  
 11)NOTE: PLEASE NOTE MDP`S ARE SHOWN AS
 277V/480 AND NO INFORMATION ON GFI
 PROTECTION, 230-95 ETC.
  
 12)NOTE: PLEASE NOTE NOT ENOUGH INFOR-
 -MATION FOR FIRE PUMP/SIZE/OCP ETC,,,,
  
 13)NOTE: PLEASE NOTE MISSING DISC MEANS
 ON LOAD SIDE OF TRANSFORMERS.240-21/
 384-16,,,
  
 14)NOTE: PLEASE NOTE TAPS ON LOAD SIDE
 OF ALL TRANSFORMERS. 240-21
  
 15)NOTE: PLEASE NOTE NOTHING SUBMITTED
 FOR GUARD HOUSE? GROUNDING? DISC MEANS
 225-31/250-32
  
 16)NOTE: PLEASE NOTE THAT NO MAINS ARE
 SHOWN FOR MDPL/MDPH.230-71/230-72/230-2
  
 17)NOTE: PLEASE NOTE NO GROUNDING ELEC-
 -TRODE. SYSTEM DETAIL SUBMITTED . 250-50
  
 18)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED.215-5 ETC
 220-3,220-10,220-11,220-13,215-3,230-42
  
 19)NOTE: PLEASE SHOW WHERE FHAR 24 CFR
 100.205 ARE SHOWN.
  
 20)NOTE: PLEASE NOTE ARC FAULT FOR
 BEDRROMS.210-12
  
 PLEASE NOTE THAT PLANS ARE NOT COMPLETE
 FOR FULL REVIEW. IF THERE ARE ANY QUESTI
 ONS, PLEASE CALL.
  