Plan Review Notes
Plan Review Notes For Permit 02060381
Permit Number 02060381
Review Stop B
Sequence Number 1
Notes
Date Text
2002-07-23 00:00:00PAID PLAN REVIEW.THE BUILDING WILL BE
 A THRESHOLD BUILDING AND WILL REQUIRE A
 THRESHOLD INSPECTOR AND A THRESHOLD
 INSPECTION PLAN.SEE FBC 105.13.
 CONTACT DON NEELY, ASSISTANT BUILDING
 OFFICIAL FOR ADDITIONAL INFORMATION
 REGARDING THRESHOLD BUILDINGS.(561)
 659-8096 EXT, 8333.
  
 THE PLANS PROVIDED ARE NOT COMPLETE NOR
 WERE ANY SPECIFICATIONS INCLUDED, THUS
 ACOMPLETE, CLOSE AND CRITICAL PLAN
 REVIEW WAS NOT POSSIBLE.FBC 104.3.1.1
 PROVIDES AN OUTLINE OF THE ITEMS
 REQUIERED FOR PLAN REVIEW AND CAN SERVE
 AS A GUIDE FOR THE BUILDING DESIGN
 PROFESSIONALS.
  
 THE BUILDING PROPOSES A MIXED OCCUPANCY
 GROUP OF R2, R4, B AND A2, USES.THE
 SITE PLAN DOES NOT INDICATE THE
 LOCATION OF THE FUTURE BLDG FOR
 DETERMINATION OF FBC TABLE 600
 REQUIREMENTS. (ASSUMED PROPERTY LINE)
  
 SHEET A101, GENERAL NOTES #12.SEE FBC
 803.2 FOR CLASSIFICATION OF INTERIOR
 FINISH.
  
 NOTES #13 AND #28, RE: FIRE PROTECTION
 AND FIRE STOPPING.SEE FBC 104.2.3 AND
 THE REQUIREMENT FOR SPECIFIC
 INFORMATION AS TO DESIGNS AND METHODS.
  
 SHEET LS- 1.01 HAS ERRONEOUS INFORMATION
 FOR THE RATINGS OF EXTERIOR BEARING
 WALLS.SEE FBC TABLE 600.(3HR)
  
 SIMILAR CONFLICTS EXIST WITH THE
 HEADING"BEAMS, GIRDERS AND ARCHES".
  
 LS - 1.01.AREAS SHOWN AS "B GROUP B"
 AND SUITES A AND B, DECLARE A SINGLE
 EXIT COMPLIANCE BASED ON AREA IN SQUARE
 FEET.SEE ALSO FBC 1004.1.2 AND FBC
 1004.1.3 AS MAY BE APPLICABLE.
  
 SUITES A AND B ARE PRESENTED AS
 "INDIVIDUAL" IT THEN FOLLOWS THAT
 CORRIDOR 134 IS A DEAD END IN EXCESS OF
 FIFTY FEET AND IS PROHIBITTED BY FBC
 1004.1.4.
  
 DOORS SHOWN AS C176, C177 AT THE PRIVATE
 DINING ROOM ARE NOT RATED AS REQUIRED
 FOR ATRIUM SEPARATION.
  
 A PARTITION DETAIL FOR THE NON-RATED
 SMOKE PARTITIONS SHOULD BE PROVIDED IN
 ACCORDANCE WITH FBC TABLE 704.2.4,
 FOOTNOTE #4.
  
 A SEATING PLAN IS NECESSARY FOR THE
 DINING, MULTI USE, AND SIMILAR ROOMS.
 SEE FBC 1003.1.2.
  
 PROVIDE CALCULATIONS FOR THE ATRIUMS,
 AND AN NARRATIVE OF THE OPERATION.
 INCLUDE A DESCIPTION OF COMPLIANCE WITH
 FBC 414.8 FOR THE INTERIOR ROOMS.
  
 FBC TABLE 410.2.2 REQUIRES ONE HOUR
 SEPARATION FOR THE MAINTENANCE ROOM
 #A144.
  
 THE RAMP IN ROOM C157, FOR THE PLATFORM,
 MUST COMPLY WITH FBC 11-4.8, INCLUDING
 HANDRAILS.
  
 THE EIFS TRIM DEPICTED IN VARIOUS
 PLACESDOES NOT COMPLY WITH FBC 1404.1.
  
 THE STRUCTURAL PLANS ARE INCOMPLETE.
 HOW WAS THE 2500 PSF SOIL BEARING VALUE
 ARRIVED AT?
  
 PLEASE NOTE THE DESIGN STANDARDS USED,
 ASSUMED LOADS AND SPECIFIC INFORMATION
 FOE THE DELEGATED DESIGN ITEMS,
 INCLUDING, TRUSSES, HAND GUARD RAILS,
 STAIRS, ETC.
  
 THE ABOVE INFORMATION SHOULD BE
 ADDRESSED IN THE ACTUAL PERMIT PLANS
 AND SPECIFICATIONS.