2002-07-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| FHA AMEND-98 DESIGN MANUAL |
| |
| 1) ROUTE PLANS TO PALM BEACH COUNTY |
| HEALTH UNIT, DIVISION OF ENVIRONMENTAL |
| HEALTH, 901 EVERNIA ST WPB 33401. (561) |
| 355 3018 BEFORE RESUBMITTING FOR PLAN |
| REVIEW. |
| 2) SHT A-201 SHOW CLEAR FLOOR SPACE FOR |
| ALL HDCP FIXTURES IN TOILET, SHOWER, |
| BATHROOMS IN DWELLINGS, AND FOR DRINKING |
| FOUNTAINS. |
| 3) SHT A-2.31 PLEASE PROVIDE CALCULAT- |
| IONS FOR PRIMARY AND SECONDARY ROOF |
| DRAINS PER SECTIONS 1106 & 1107. ADD 1/2 |
| AREA OF ALL VERTICAL WALLS AND ALL ROOF |
| AREA THAT IS DRAINING FROM ABOVE. SHOW |
| SIZE FOR ALL SCUPPERS. |
| 4) SHT A-8.03 SHOW CONTROL HEIGHT ON |
| SHOWER DETAIL. 11-4.21.5 |
| 5) SHT A-8.05 TOILET ROOM DETAILS NUMB- |
| ERS 1, 2, 3, 4, 5, 6, & 7, DOORS SHALL |
| NOT SWING INTO CLEAR FLOOR SPACE OR UN- |
| OBSTRUCTED TURNING RADIUS OF ANY FIXTURE |
| WATER CLOSET SHALL BE 1'6" OFF WALL TO |
| CENTER OF FIXTURE. WATER CLOSED SHALL |
| NOT INTRUDE INTO 5' TURNING RADIUS. |
| PLEASE SHOW ON DETAILS. |
| 6) SHT P-101 DETAIL 3/P-001 WATER HEATER |
| "A" DETAIL. WATER HEATER PIPING SHOULD |
| BE CONFIGURED TO FEED AND DRAIN FROM |
| EACH WATER SIMULTANIOUSLY. THEY SHOULD |
| BE PIPED IN PARALLEL NOT IN SERIES AS |
| SHOWN. SEE MANUFACTURE INSTALLATION IN- |
| FORMATION. (HEATERS SHOULD BE COMPANION, |
| NOT SLAVE HEATERS)(SEE SHT P-102) |
| 7) SHT P-101 DETAIL 3/P-001 WATER HEATER |
| "A" DETAIL, BOTTOM FED WATER HEATERS |
| SHALL HAVE A VACUUM RELIEF VALVE INSTALL |
| ED. |
| 8) SHT P-101 DETAIL 3/P-001 WATER HEATER |
| "A" DETAIL, A MEANS OF CONTROLLING THERM |
| AL EXPANSION IS REQUIRED. SEC 607.3.2. |
| 9) SECOND SHT P-101 SANITARY FLAT DRAW- |
| ING, CLEAN OUTS SHALL BE LOCATED MAXIMUM |
| 100', MORE ARE REQUIRED. |
| 10) SECOND SHT P-101 WATER LINES FLAT |
| DRAWING, DOUBLE VALVES TO WATER LINES |
| FEEDING JANITOR CLOSET (D110) AND SHOW- |
| ER ROOM (D112). NO VALVES TO KITCHEN |
| WATER (D201) |
| 11) SHT P-102 BACKFLOW REQUIRED FOR |
| WATER LINE TO FOUNTAIN. |
| 12) SHT P-102 SANITARY RISER, BLDG DRAIN |
| MAXIMUM 100' FOR CLEANOUTS. MORE REQUIR- |
| ED. SHOW ON RISERS. |
| 13) SHT P-105 WATER RISER DIAGRAM, WATER |
| HAMMER ARRESTORS REQUIRED FOR ALL QUICK |
| CLOSING VALVES, (DISHWASHERS, WASH MACHI |
| NES, AND ICE MAKERS), AND SHALL BE LOCA- |
| TED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" NOT AT TOP OF DROP. PLEASE SHOW |
| ON WATER RISER. SEC 604.9 |
| 14) PLEASE PROVIED A SANITARY RISER DIA- |
| GRAM FOR BLDG DRAIN. SHOW TOTAL FIXTURE |
| UNITS AS THEY ACCUMULATE IN SYSTEM. |
| 15) PLEASE PROVIDE A STORM RISER DIAGRAM |
| WITH ALL SQ FT AND SHOW AS IT ACCUMULAT- |
| ES IN SYSTEM. |
| 16) PLEASE PROVIDE CONDENSATE RISER |
| DIAGRAM. PROVIDE DETAILS FOR CONDENSATE |
| EXITING BLDG. RELIEF VENTS REQUIRED. SHT |
| 5 CIVIL SHOWS ROOF DRAIN TIE IN FOR COND |
| PLEASE CHANGE TO SHOW CONDENSATE TIE IN. |
| 17) ALL DWELLING UNITS SHALL COMPLY WITH |
| FHA AMEND-98 DESIGN MANUAL. PLEASE SHOW |
| COMPLIANCE WITH REQUIREMENTS 1 THRU 7 |
| AND SPECIFY SPECIFICATION "A" OR "B" FOR |
| BATHROOMS. SEE DESIGN MANUAL FOR TYPICAL |
| A OR B BATHROOM LAYOUTS. |
| 18) SHT P-102 FOUNTAIN. PLEASE SHOW |
| RISER FOR FOUNTAIN. FOUNTAIN DRAIN SHALL |
| DRAIN TO SANITARY, AND OVERFLOW SHALL |
| DRAIN TO STORM. PLEASE PROVIDE DETAILS. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT 8377 |