Plan Review Notes
Plan Review Notes For Permit 02060379
Permit Number 02060379
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-07-16 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3) PLEASE CLEARLY ILLUSTRATE FIRE LANES
 FOR THE BUILDING.
  
 4) A KNOX-BOX WILL BE REQUIRED FOR THE
 BUILDING.
  
 5) PLEASE INDICATE HOW THE BUILDING WILL
 BE LICENSED BY THE STATE, COUNTY, AND
 THE CITY.
  
 6) PLEASE CLEARLY IDENTIFY TRAVEL
 DISTANCES TO EXITS, AND EXIT DISCHARGE
 LOCATIONS.
  
 7) BUILDING ADDRESS REQUIRED ON
 BUILDING. NUMERALS TO BE AT LEAST 6"
 HIGH.
  
 8) COVERED DROP-OFF IS NOT HIGH ENOUGH
 IF FIRE RESCUE UNITS ARE EXPECTED TO
 USE IT. MINIMUM ELEVATION MUST BE AT
 LEAST 13'- 6" HIGH.
  
 9) PLEASE INDICATE OCCUPANT LOADS FOR
 THE BUILDING INCLUDING STAFF TOTALS.
  
 10) ARE DOOR SWINGS IN THE PROPER
 DIRECTIONS ADJACENT TO DINING ROOMS
 D251 AND D211.
  
 11) LINEN AND ELECTRICAL ROOM CLOSETS
 APPEAR TO SWING TO FAR INTO CORRIDORS
 D214 AND D254.
  
 12) FIRE SPRINKLER PLANS ARE INCOMPLETE.
 PLANS DO NOT SHOW FIRE SPRINKLER HEADS,
 PIPING OR OTHER APPURTENANT EQUIPMENT.
 NO FIRE DEPARTMENT CONNECTION SHOWN.
 ALSO NO HYDRAULIC CALCULATIONS WERE
 PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910