2002-06-24 00:00:00 | ************ UNSAT ****************** |
| |
| 1)NOTE: PLEASE NOTE MISSING GROUNDING |
| ELECTRODE FOR DETACHED "GUARDHOUSE" |
| 250-32. |
| |
| 2)NOTE: PLEASE NOTE PANELS SHOWN IN |
| "STORAGE ROOM" ON E-102. PLEASE NOTE |
| NO STORAGE PER 110-26/384-7 |
| |
| 3)NOTE: PLEASE NOTE PANELS SHOWN IN |
| "STORAGE ROOM ON E-104 "D137". |
| 110-26/384-7. |
| |
| 4)NOTE: PLEASE PROVIDE MORE DETAIL FOR |
| GROUNDING OF TRANSFORMER AND PANEL "DP" |
| ATTACHMENT ETC. 250-30 |
| |
| 5)NOTE: PLEASE NOTE NO LOAD CALCULATIONS |
| WERE SUBMITTED? PER 220 |
| |
| 6)NOTE: PLEASE NOTE PANEL FOR GUARD |
| HOUSE NOT SHOWN FOR WHERE FEED IS COMING |
| FROM?? |
| |
| 7)NOTE: PLEASE NOTE PANEL DP NOTE SAYS |
| COMING FROM MDP? PLEASE NOTE MDP NOT |
| SHOWN/LOAD ETC ETC?? |
| |
| 8)NOTE: PLEASE CLARIFY PANELS LSH,EQ |
| SHOWN AS MLO W/ MAIN BRKRS?? |
| |
| 9)NOTE: PLEASE CLARIFY HOW NOTE FOR |
| EM LTS AND EXIT LTS SAYS COMING FROM EM |
| PANEL AND NOTHING IS SUBMITTED FOR |
| REVIEW FOR EM BACK UP POWER RISER? |
| PLANS ALSO NOTE LSH/EQ COMING FROM |
| OTHER LCOATIONS, BUT NO INFORMATION WAS |
| SUBMITTED FOR REVIEW. LOAD CALCS FOR |
| FEEDS FROM EXSITING??? |
| |
| PLEASE COMPLETE PLANS FOR COMPLETE |
| REVIEW. PLEASE SUBMIT ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |