Plan Review Notes For Permit 02060361 |
Permit Number |
02060361 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-07-06 00:00:00 | PLAN DENIED | | 1) ENERGY CALCS AND PLANS DO NOT MATCH | | ON A/C EQUIPMENT SEER | | 2) NEED LETTER FROM MANUFACTURE STATING | | THAT UNDER ANY CONDITION THE | | AIRHANDLER WILL NOT PRODUCE 2000 CFM | | 3) REFER TO SECTION 601.4 BALANCED | | RETURN AIR | | 4) VARIFY TYPE OF VENTILATION USED FOR | | FRESH AIR SECTION 402 NATURAL OR | | SECTION 403 MECHANICAL FBC.2001 | | 5) CALCULATION FOR TYPE OF VENTILATION | | USED | | PLAN REVIEW BY HAROLD MOSER | | (561)659-8096 EXT.8390 |
|