2002-06-18 00:00:00 
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.