Plan Review Notes
Plan Review Notes For Permit 02060290
Permit Number 02060290
Review Stop E
Sequence Number 4
Notes
Date Text
2002-12-10 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE NECESSARY CHANGES TO
 PLANS, AND RESUBMIT FOR REVIEW WITH AS-
 BUILTS,PRIOR TO ROUGH INSPECTION.
  
 1} THE GARAGE OUTLETS ARE REQUIRED TO BE
 GFI PER 210-8(A)(6).
  
 2} PROVIDE AN EGRESS LIGHT FOR THE
 GARAGE PER 210-70(A)(2).
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 4} THE SMOKE DETECTOR LOCATED IN THE
 HALL MUST BE LOCATED AT MORE THAN
 3'FROM THE BATHROOM DOOR PER NFPA-72
 8-1.4.2.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.AND 210-8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT 8392