Plan Review Notes
Plan Review Notes For Permit 02060290
Permit Number 02060290
Review Stop E
Sequence Number 2
Notes
Date Text
2002-09-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE ANY NECESSARY CHANGES
 ON THE DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} THE WASHER,DRYER AND RANGE RECEPTACLE
 LOCATIONS ARE NOT SHOWN ON THE DRAWINGS
  
 2} THE DISHWASHER/DISPOSAL RECEPTACLES
 ARE NOT SHOWN ON THE PLAN.
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 6} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 8} ALL SMOKE DETECTORS TO COMPLY WITH
 NFPA-72,CHAPTER 8,1999.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392