Plan Review Notes For Permit 02060290 |
Permit Number |
02060290 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-09-04 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION MAKE ANY NECESSARY CHANGES | | ON THE DRAWINGS AND RESUBMIT FOR REVIEW. | | | | 1} THE WASHER,DRYER AND RANGE RECEPTACLE | | LOCATIONS ARE NOT SHOWN ON THE DRAWINGS | | | | 2} THE DISHWASHER/DISPOSAL RECEPTACLES | | ARE NOT SHOWN ON THE PLAN. | | | | 3} PLEASE NOTE FRONT AND REAR | | RECEPTS REQ`D PER 210-52E | | | | 4} PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | 6} PLEASE NOTE KITCHEN COUNTER- | | -SPACE RECEPT SPACING SHALL MEET ART; | | 210-52C 1,2,3,4,AND 5. | | | | 7} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | 8} ALL SMOKE DETECTORS TO COMPLY WITH | | NFPA-72,CHAPTER 8,1999. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|