2002-07-12 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 02060290 |
| ADD:707 39TH ST (REAR UNIT) |
| CONT: KENCUO DEV CORP INC |
| TEL: 784-8618 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)ALL INFORMATION, DRAWINGS, SPECIF- |
| ICATIONS AND ACCOMPANYING DATA SHALL |
| BEAR THE NAME AND SIGNATURE & TELEPHONE |
| NUMBER OF THE PERSON RESPONSIBLE FOR |
| THE DRAWING OF THE PLANS, CITY AMEND |
| 104.2.1. |
| |
| 2) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, NOTES |
| INDICATE THE 2002 FL BLDG CODE, CURRENT |
| EDITION 201 FL BLDG CODE. |
| |
| 4) PROVIDE 2 CURRENT COPIES OF SIGNED & |
| SEALED SURVEYS WITH PROPOSED IMPROVEMENT |
| TO BE COMPLETED. |
| |
| 5) EXISTING GARAGE HAS TO MAINTAIN THIS |
| USAGE PER THE CITY ZONING CODE, ONE END |
| MAY BE BLOCKED IN, PROVIDE (2) COPIES OF |
| CURRENT PRODUCT TESTING REPORT FOR THE |
| OVERHEAD DOOR.SBCCI OR DADE COUTNY |
| REPORTS ARE ACCEPTED. |
| |
| 6)411.2.8. OPENINGS FROM A PARKING |
| GARAGE DIRECTLY INTO A ROOM FOR SLEEPING |
| PURPOSES SHALL NOT BE PERMITTED. |
| |
| 7)905.2.1 APPROVED SINGLE-STATION OR |
| MULTIPLE STATION SMOKE DETECTORS SHALL |
| BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| CHAPTER 2, WITHIN EVERY DWELLING UNIT |
| WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, |
| OR TOWNHOUSE AND EVERY GUEST OR SLEEPING |
| ROOM IN A MOTEL, HOTEL, OR DORMITORY & |
| SLEEPING ROOMS IN RESIDENTIAL CARE/ |
| ASSISTED LIVING OCCUPANCIES. WHERE MORE |
| THAN ONE DETECTOR IS REQUIRED TO BE |
| INSTALLED WITHIN INDIVIDUAL DWELLING |
| UNIT, THE DETECTOR SHALL BE WIRED IN |
| SUCH A MANNER THAT THE ACTUATION OF ONE |
| ALARM WILL ACTIVATE ALL THE ALARMS IN |
| THE INDIVIDUAL UNIT. |
| |
| 8) INDICATE THE BEDROOM WINDOW SIZE FOR: |
| 2001 FL BLD CODE, 1005.4: |
| PROVIDE EMERGENCY EGRESS WINDOWS IN |
| SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| OPENING HEIGTH OF 24" AND NET CLEAR |
| OPENING WIDTH OF 20" AND A NET CLEAR |
| OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| OPENINGS ARE PERMITTED TO HAVE A NET |
| CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| SHALL NOT BE MORE THAN 44 " ABOVE THE |
| FINISH FLOOR. |
| |
| 9) INDICATE THE SIZE WINDOW OPEN AREA |
| FOR BATH ROOM, OR IS MECHANICAL VENTILAT |
| ION TO BE REQQUIRED? 1203.4.2/1203.5. |
| |
| 10) 1204.1 FIXTURES, MISSING LAV IN BATH |
| ROOM. SEE PLUMB 403.1 TABLE. |
| |
| 11)DOES THE TUB INCLUDE A SHOWER UNIT? |
| 1204.4 |
| |
| 12) CHAPTER 13, RESIDENTIAL BUILDING |
| COMPLIANCE, FORM 600 3.C IS TO BE USED |
| FOR RESIDENTIAL RENOVATIONS 600 SQ FT OR |
| LESS UNDER AIR.THIS IS A PERSCRIPTIVE |
| METHOD WHERE TABLES 6C-1 & 6C-2 APPLY. |
| |
| 13)1503.3 COPING. PARARET WALLS SHALL |
| BE PROPERLY COPED WITH NONCOMBUSTIBLE |
| MATERIALS OF A WIDTH NO LESS THAN THE |
| THICKNESS OF THE PARAPET WALL. |
| |
| 14) 1503.4.4 PROTECTION AGAINST DECAY & |
| TURMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 15) FIGURE 1606 WIND-BORNE DEBRIS |
| REGION; INDICATES THAT W.P.B. CITY OF IS |
| LOCATED IN THE 140 MPH ZONE. PLANS ARE |
| TO INDICATE THIS. |
| |
| 16) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 17)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. |
| A) OVERHEAD GARAGE DOOR |
| B) WINDOWS |
| C) MULLIONS |
| D) EXTERIOR DOORS |
| E) STORM SHUTTERS |
| |
| 18)FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 19) 1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. |
| |
| 20) 1707.3.1 JOIST HANGERS, FRAMING |
| ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| LABELED AND LISTED FOR THEIR LOAD CARRY- |
| ING CAPACITY. PLANS DO NOT INDICATE THE |
| SIZE OF FRAMING MEMBERS, SPANS, TYPE OF |
| DEVICE TO BE USED TO RESIST UPLIFT LOADS |
| NOR GRAVITY LOADS. THERE IS NO INFORMA- |
| TION ON THE TEMPORARY BRACING WHEN THE |
| ROOF FRAMING IS REPAIRED. NO INFORMATION |
| ON THE TIMBERS TO BE SISTERED IN AS TO |
| LAPS NAILING SIZE OR PATERNS, ETC.NO |
| INFORMATION AS TO EXTERIOR WALLS, WALL |
| SECTIONS ROOF FRAMING DETAILS, FOR CBS |
| AND FRAME WALLS (GARAGE). |
| |
| 21) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 22) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 23) 2304.5 CLEARENCE BETWEEN WOOD SIDING |
| & EARTH ON THE EXTERIOR OF A BUILDING |
| SHALL NOT BE LESS THAN 6" EXCEPT WHERE |
| SIDING, SHEATHING AND FRAME WALL ARE OF |
| APPROVED DURABLE WOOD OR APPROVED PRE- |
| SERVATIVE TREATED WOOD. (GARAGE WOOD |
| WALLS). WHAT TYPE OF EXTERIOR FINISH? |
| |
| 24) POSSIBLE TABLE 600 ISSUES THERE |
| IS NO REAR ELEVATION, INDICATING THE |
| AMOUNT OF OPENINGS SIZES INCLUDING WHICH |
| END OF GARAGE IS TO BE CLOSED? |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |