Plan Review Notes For Permit 02060289 |
Permit Number |
02060289 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-09-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SHT 1 OF 5 ALL SHOWERS SHALL BE A MIN | | OF 900 SQ INCHES AND MIN OF 30" WIDE | | FINISHED INSIDE DIAMETER. SEC 4.17.4 | | 2) SHT 1 0F 5 ALL WATER CLOSETS SHALL BE | | SET AT 15" OFF THE WALL AND SHALL HAVE | | 18" CLEARANCE IN FRONT OF THE W/C AND | | ALSO THE LAV. SEC 405.3.1 | | 3) TABLE 403.1 MINIMUM FACILITIES REQ'S. | | A WASH MACHINE HOOK-UP WATER AND SANIT. | | PLEASE SHOW WHERE THE HOOK-UP IS LOCATED | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|