Plan Review Notes
Plan Review Notes For Permit 02060289
Permit Number 02060289
Review Stop E
Sequence Number 2
Notes
Date Text
2002-09-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 AS MENTIONED IN THE PREVIOUS REVIEW,THE
 SCOPE OF THE ELECTRICAL WORK IS NOT
 CLEAR.CAN'T TELL THE EXISTING WORK FROM
 THE NEW WORK,PLEASE CLARIFY.
  
 PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
 SAME COMMENT FROM LAST REVIEW NOTE#2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392