2002-09-04 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02060289 |
| ADD: 707 39TH ST (FRONT BUILD) |
| CONT: KENACO DEV CORP INC |
| TEL: (561)784-8618 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) WHAT OCCUPANCY USE WILL THIS BE? |
| A) R-3 SINGLE FAMILY OCCUPANCY |
| B) R-3 ROOMING HOUSE (NOT TRANSIENT) |
| C) R-2 ROOMINGHOUSE (TRANSIENT) |
| D) R-1 BOARDING HOUSE (TRANSIENT) |
| |
| 2) AS STATED IN THE OPENING STATEMENT, |
| LIST WORK TO BE ACCOMPLISHED ON THE |
| INTERIOR, AS WELL AS EXTERIOR. |
| |
| 3) 3401.7.2 REPAIRS AND ALTERATIONS, |
| AFTER AN ACCURATE DESCRIPTION OF WORK |
| THAT SHALL BE COMPLETED UNDER THIS PER- |
| MIT ATRUE ASSESSMENT OF THE DOLLAR |
| VALUE CAN BE DERIVED FOR WORKTO BE PER- |
| MITTED. THIS SECTION OF THE CODE DETER- |
| MINES AS TO WHAT SHALL BE REQUIRED TO BE |
| BROUGHT UP TO CODE BY THE PERCENT OF |
| WORK ACCOMPLISHED (DOLLAR VALUE) VS THE |
| VALUE OF THE EXISING BUILDING. |
| |
| 4) 1203.2.5 KITCHENS SHALL BE NO LESS |
| THAN 7 FT IN ANY DIRECTION. |
| |
| 5) 1203.4.1 TOLIET ROOMS SHALL NOT OPEN |
| DIRECTLY INTO A ROOM USED FOR THE PREP- |
| ARATION OF FOOD FOR SERVICE TO THE |
| PUBLIC. OCCUPANCY USE SHALL DETERMINE |
| IF THIS SECTION IS APPLICABLE. |
| |
| 6) MISSING PRODUCT TESTING REPORTS FOR |
| ALL EXTERIOR DOORS & GLAZED OPENINGS. |
| 2 SETS OF PRODUCT TESTING REPORTS ARE |
| REQUIRED FOR EACH BUILDING, SINCE THEY |
| ARE UNDER SEPERATE PERMIT!!!!!!! |
| |
| 7) 1007.4.2 STAIRS SHALL HAVE FLOORS OR |
| LANDINGS AT DOOR OPENINGS. MISSING AT |
| THE FRONT ENTRY AND FIRST FLOOR PROPOSED |
| KITCHEN. |
| |
| 8) 1007.5.1 HANDRAILS REQUIRED FOR |
| STAIRWAY, GRIPPING SURFACES SHALL BE |
| CONTINUOUS, WITHOUT INTERRUPTION BY |
| NEWEL POST OR OTHER OBSTRUCTIONS. |
| |
| 9) 1007.5.5 HANDRAILS SHALL EXTEND AT |
| LEAST 12" HORIZONTALLY BEYOND THE TOP |
| RISER OF A FLIGHT . AT THE BOTTOM, THE |
| HANDRAIL SHALL BE CONTINUE TO THE SLOPE |
| FOR A DISTANCE OF THE DEPTH OF ONE TREAD |
| FROM THE BOTTOM RISER. EXCEPTION, |
| HANDRAILS IN A DWELLING UNIT. OCCUPANCY |
| SUB-CLASSIFICATION SHALL DETERMINE! |
| |
| 10) UPPER FLOOR PLAN IS THE DETAIL FOR A |
| "ALTERNATE KITCHEN" TO BE USED FOR THE |
| SECOND FLOOR MAKING 2 KITHENS FOR THIS |
| BUILDING? |
| |
| PLANS ARE NOT THROUGH ENOUGH TO DO A |
| COMPLETE REVIEW. PLEASE ADDRESS THE |
| ABOVE ISSUES. BECAUSE OF NOT ANSWERING |
| THE SAME COMMENTS FROM THE FIRST REVIEW |
| ADDITIONAL COMMENTS MAY APPEAR FOR THE |
| FIRST TIME ON THE NEXT REVIEW!!!! |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X 8412 |