Plan Review Notes For Permit 02060280 |
Permit Number |
02060280 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-07-31 00:00:00 | MECHANICAL PERMIT 02060348 | | | | SHOULD GAS DRYER BE INSTALLED - | | SHOW COMPLIANCE FOR COMBUSTION AIR AS | | PER 2001 FBC(M) CHAPTER 7. | | | | SMOKE DETECTORS SHALL BE INSTALLED | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | UPON ACTIVATION, THE SMOKE DETECTORS | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | SYSTEM. 2001 FBC(M) 606.4 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|