2002-08-21 00:00:00 | ************* NOTE/PROVISO/REVISION**** | | | | 1)NOTE: PLEASE NOTE SERVICE ENTRANCE | | CONDUCTORS SHOWN AS 3-#10`S. PLEASE SEE | | 310-15/ 310-16 FOR CORRECT SIZING. | | | | PLEASE REVISE RISER DIAGRAM AND ANY | | OTHER CHANGES ON PLANS BEFORE FINAL. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|