2002-07-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02060268
 ADD: 7113 EAGLE TERRACE
 CONT: A R CUSTOM HOMES INC
 TEL: (561)721-2270
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)-2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR. SECOND FLOOR BONUS ROOM
 REQUIRES AN EMERGENCY EGRESS WINDOW.
 THE CASEMENT WINDOW DOESN'T MAKE THE 20"
 CLEAR HORIZONTAL MEASUREMENT. SEE PAGE
 11 OF 12 PRODUCT APPROVAL FOR DIMINSION
 OF EXTRUDED FRAME. THE SECOND FLOOR
 ELEMENT SHALL ALSO REQUIRE A CLEAR OPEN-
 ING OF 5.7 SQ FT.
  
 2) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 2001 FBC 2406.2. SHEET 5B
 INDICATES UNDER"WIND PRESSURE ANALYSIS"
 BUTT GLASS SEE SHEET S-2 FOR RATIONAL
 ANALYSIS. MISSING STRUCTURAL SHEETS!!!
 A) LIVING ROOM
 B) MORNING ROOM
 C) MASTER BATH SHOWER
  
 3) DISCREPANCIES, SHEET A-5 INDICATES
 THE USE OF BUTT GLAZING IN THE LIVING
 ROOM AND MORNING ROOM A HEIGTH OF 144"'
 WHILE SHEET A-6 INDICATES THE USE OF A
 HORIZONTAL MULLION @ 10'-0" FOR BOTH
 CASES?
  
 4)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 5) SHEET A-5A BONUS RM # 2 MISSING SMOKE
 DETECTOR IN ROOM.
  
 6)- FL BL CODE 905.2.1 SMOKE DETECTORS,
 WHERE MORE THAN 1 SMOKE DETECTOR IS
 REQUIRED TO BE INSTALLED WITHIN DWELLING
 UNITS, THE DETECTORS SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTIVATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 7) FL ENERGY CODE MISSING INSULATION
 UNDER THE 2ND STORY FLOOR, ALSO NOT INCL
 UDED ON ENERGY SHEET.
  
 8) SHEET 6-C TRUSS LAYOUT MISSING THE
 MAGNITUDE OF LOADS TO BE RESISTED,
 VERTICAL, HORIZONTAL & LATERAL.
  
 9) 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127. PROVIDE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026