2002-07-02 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02060268 |
| ADD: 7113 EAGLE TERRACE |
| CONT: A R CUSTOM HOMES INC |
| TEL: (561)721-2270 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)-2001 FL BLD CODE, 1005.4: |
| PROVIDE EMERGENCY EGRESS WINDOWS IN |
| SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| OPENING HEIGTH OF 24" AND NET CLEAR |
| OPENING WIDTH OF 20" AND A NET CLEAR |
| OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| OPENINGS ARE PERMITTED TO HAVE A NET |
| CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| SHALL NOT BE MORE THAN 44 " ABOVE THE |
| FINISH FLOOR. SECOND FLOOR BONUS ROOM |
| REQUIRES AN EMERGENCY EGRESS WINDOW. |
| THE CASEMENT WINDOW DOESN'T MAKE THE 20" |
| CLEAR HORIZONTAL MEASUREMENT. SEE PAGE |
| 11 OF 12 PRODUCT APPROVAL FOR DIMINSION |
| OF EXTRUDED FRAME. THE SECOND FLOOR |
| ELEMENT SHALL ALSO REQUIRE A CLEAR OPEN- |
| ING OF 5.7 SQ FT. |
| |
| 2) PROVIDE ENGINEERING FOR BUTT GLASS |
| ASSEMBLIES PER 2001 FBC 2406.2. SHEET 5B |
| INDICATES UNDER"WIND PRESSURE ANALYSIS" |
| BUTT GLASS SEE SHEET S-2 FOR RATIONAL |
| ANALYSIS. MISSING STRUCTURAL SHEETS!!! |
| A) LIVING ROOM |
| B) MORNING ROOM |
| C) MASTER BATH SHOWER |
| |
| 3) DISCREPANCIES, SHEET A-5 INDICATES |
| THE USE OF BUTT GLAZING IN THE LIVING |
| ROOM AND MORNING ROOM A HEIGTH OF 144"' |
| WHILE SHEET A-6 INDICATES THE USE OF A |
| HORIZONTAL MULLION @ 10'-0" FOR BOTH |
| CASES? |
| |
| 4)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. |
| |
| 5) SHEET A-5A BONUS RM # 2 MISSING SMOKE |
| DETECTOR IN ROOM. |
| |
| 6)- FL BL CODE 905.2.1 SMOKE DETECTORS, |
| WHERE MORE THAN 1 SMOKE DETECTOR IS |
| REQUIRED TO BE INSTALLED WITHIN DWELLING |
| UNITS, THE DETECTORS SHALL BE WIRED IN |
| SUCH A MANNER THAT THE ACTIVATION OF ONE |
| ALARM WILL ACTIVATE ALL THE ALARMS IN |
| THE INDIVIDUAL UNIT. |
| |
| 7) FL ENERGY CODE MISSING INSULATION |
| UNDER THE 2ND STORY FLOOR, ALSO NOT INCL |
| UDED ON ENERGY SHEET. |
| |
| 8) SHEET 6-C TRUSS LAYOUT MISSING THE |
| MAGNITUDE OF LOADS TO BE RESISTED, |
| VERTICAL, HORIZONTAL & LATERAL. |
| |
| 9) 2806.1.2 FACTORY BUILT FIREPLACES |
| SHALL BE TESTED IN ACCORDANCE WITH AND |
| MEET THE REQUIREMENTS OF UL 127. PROVIDE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |