2002-06-13 00:00:00 | DENIED; | | PAGE 4-C PLUMBING RISER. | | 1.BIDET NOT VENTED. | | 2.SECOND FLOOR KITCHEN SINK BRANCH IS | | NOT TO CODE AS DRAWN. | | 3.DRAINS IN UTILITY ROOM AND ICE MAKER, | | ARE THEY FLOOR DRAINS? IF SO WHAT SIZE | | AND MUST HAVE TRAP PRIMERS OR BE DEEP | | SEAL TRAPS. | | 4SIZE ALL VENTS | | 5.TOTAL FIXTURE COUNT IS 38.5FUS, IF 3" | | SEWER IS RUN A NOT IS REQUIRED, SLOPE | | MUST BE 1/4' PER FOOT. | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 659-8096 EXT. 8369 |
|