Plan Review Notes
Plan Review Notes For Permit 02060268
Permit Number 02060268
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-18 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM,
 PANEL SCHEDULE,LOAD CALCULATIONS, DO NOT
 CORRELATE. 180A , 200A, 300A??? SHOWN IN
 DIFFERENT LOCATIONS??
  
 2)NOTE: PLEASE NOTE THAT THERE ARE FOUR
 SMALL APPL CIRCUITS SHOWN IN LOAD CALCS
 AND ONLY TWO ON PANEL SCHEDULE?
  
 3)NOTE: PLEASE NOTE LOAD FOR AHU HEAT IS
 SHOWN AT 10KW AND HAS AN OCP OF 50A?
 PLEASE SEE SIZING OF OCP PER 424-3-B
  
 4)NOTE: PLEASE NOTE LAYOUT FOR HOUSE
 DOES NOT CORRELATE WITH MECH PLAN?
 WHICH ONE? PLEASE SHOW COND UNITS AND
 AHU`S ON ELECTRICAL PLAN WITH REQ`D DISC
 `S PER 440-11.
  
 5)NOTE: PLEASE NOTE DEPENDING ON WHAT
 SIZE OF OCP IS FINALLY SHOWN , PLEASE
 SIZE SERVICE ENTRANCE CONDUCTORS. PLEASE
 ALSO NOTE/CLARIFY (4) CONDUCTORS FROM
 METER TO PANEL FOR SINGLE PHASE SERVICE.
 PLEASE CLARIFY.
  
 6)NOTE: PLEASE SHOW AND SIZE GROUNDING
 ELECTRODE CONDUCTOR PER 250-66.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 8) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING ONLY A COUPLE.
  
 9)NOTE: PLEASE NOTE MISSING SD OUTSIDE
 BR#2.
  
 10)NOTE:PLEASE CLARIFY IF A 42 CIRCUIT
 PANEL IS 200A OR 225A??
  
 11)NOTE: PLEASE NOTE MIN KVA FOR LAUNDRY
 CIRCUIT SHALL BE 1500W. PLEASE REVISE
  
 12)NOTE: PLEASE NOTE POOL EQUIPMENT IS
 SHOWN AT 4500W AND SHOWN ON PANEL SCHED-
 -ULE AS 20A AND #12AWG?? PLEASE CLARIFY.
  
 13)NOTE: PLEASE NOTE, NOTE BELOW PANEL
 SCH, MENTIONS, USE "TW" FOR LARGER THAN
 #8?? PLEASE SEE NEC IN MANY LOCATIONS
 FOR USE OF "TW" PLEASE ALSO NOTE SIZING
 OF CONDUCTORS PER 60 DEGREE RATINGS PER
 310-16. MOST OF WIRING USED TODAY IS
 NOT TW.
  
 14)NOTE: PLEASE CLARIFY SQ FT OF HOUSE,
 LOAD CALCS SHOW 6775 AND COVER SHEET
 SHOWS 6034?
  
 15)NOTE: PLEASE NOTE ELECTRICAL PLAN
 SHOWN FOR SECOND FLOOR IS NOT CLEAR WITH
 ALL BLDG SPECS PRINTED OVER. PLEASE ALSO
 NOTE PRINTING SEEMS TO HAVE MISSED PART.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW