2002-06-18 00:00:00 | **************** UNSAT ***************** |
| |
| 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM, |
| PANEL SCHEDULE,LOAD CALCULATIONS, DO NOT |
| CORRELATE. 180A , 200A, 300A??? SHOWN IN |
| DIFFERENT LOCATIONS?? |
| |
| 2)NOTE: PLEASE NOTE THAT THERE ARE FOUR |
| SMALL APPL CIRCUITS SHOWN IN LOAD CALCS |
| AND ONLY TWO ON PANEL SCHEDULE? |
| |
| 3)NOTE: PLEASE NOTE LOAD FOR AHU HEAT IS |
| SHOWN AT 10KW AND HAS AN OCP OF 50A? |
| PLEASE SEE SIZING OF OCP PER 424-3-B |
| |
| 4)NOTE: PLEASE NOTE LAYOUT FOR HOUSE |
| DOES NOT CORRELATE WITH MECH PLAN? |
| WHICH ONE? PLEASE SHOW COND UNITS AND |
| AHU`S ON ELECTRICAL PLAN WITH REQ`D DISC |
| `S PER 440-11. |
| |
| 5)NOTE: PLEASE NOTE DEPENDING ON WHAT |
| SIZE OF OCP IS FINALLY SHOWN , PLEASE |
| SIZE SERVICE ENTRANCE CONDUCTORS. PLEASE |
| ALSO NOTE/CLARIFY (4) CONDUCTORS FROM |
| METER TO PANEL FOR SINGLE PHASE SERVICE. |
| PLEASE CLARIFY. |
| |
| 6)NOTE: PLEASE SHOW AND SIZE GROUNDING |
| ELECTRODE CONDUCTOR PER 250-66. |
| |
| 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 8) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING ONLY A COUPLE. |
| |
| 9)NOTE: PLEASE NOTE MISSING SD OUTSIDE |
| BR#2. |
| |
| 10)NOTE:PLEASE CLARIFY IF A 42 CIRCUIT |
| PANEL IS 200A OR 225A?? |
| |
| 11)NOTE: PLEASE NOTE MIN KVA FOR LAUNDRY |
| CIRCUIT SHALL BE 1500W. PLEASE REVISE |
| |
| 12)NOTE: PLEASE NOTE POOL EQUIPMENT IS |
| SHOWN AT 4500W AND SHOWN ON PANEL SCHED- |
| -ULE AS 20A AND #12AWG?? PLEASE CLARIFY. |
| |
| 13)NOTE: PLEASE NOTE, NOTE BELOW PANEL |
| SCH, MENTIONS, USE "TW" FOR LARGER THAN |
| #8?? PLEASE SEE NEC IN MANY LOCATIONS |
| FOR USE OF "TW" PLEASE ALSO NOTE SIZING |
| OF CONDUCTORS PER 60 DEGREE RATINGS PER |
| 310-16. MOST OF WIRING USED TODAY IS |
| NOT TW. |
| |
| 14)NOTE: PLEASE CLARIFY SQ FT OF HOUSE, |
| LOAD CALCS SHOW 6775 AND COVER SHEET |
| SHOWS 6034? |
| |
| 15)NOTE: PLEASE NOTE ELECTRICAL PLAN |
| SHOWN FOR SECOND FLOOR IS NOT CLEAR WITH |
| ALL BLDG SPECS PRINTED OVER. PLEASE ALSO |
| NOTE PRINTING SEEMS TO HAVE MISSED PART. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE NAY QUESTIONS, |
| PLEASE CALL. |
| |