2002-08-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.NO OTHER
 RECEPTACLES OUTSIDE THE ROOM.
  
 3} PLEASE NOTE THAT AN EQUIPMENT
 GROUNDING CONDUCTOR IS REQUIRED FROM
 THE DISCONNECT TO THE PANEL UNLESS THE
 CONDUIT IS METAL AND BONDED.
  
 4} PLEASE INDICATE THE LOCATION OF THE
 SERVICE ON THE DRAWING.
  
 5} NOTE THAT A RECEPTACLE IS REQUIRED
 IN BEDROOM #2 TO COMPLY WITH
 210-52(A)(1)(A).
  
 6} PLEASE NOTE THAT ALL KITCHEN
 COUNTERTOP RECEPTACLES MUST BE
 GFI'S.(ONE NOT LABLED )
  
 7} PLEASE CHECK THE CLEARANCE BETWEEN
 THE PANEL AND THE WATER HEATER TO
 COMPLY WITH 110-26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392