2002-08-16 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE CODE COMPLIANCE FORMS |
| |
| 4) THE SUBMITTED PRO-PANEL II PRODUCT |
| APPROVAL IS FOR A WALL SYSTEM AND IS NOT |
| APPLICABLE TO THE PROPOSED PRO-PANEL II |
| METAL ROOFING.SUBMIT AN APPROPRIATE |
| ROOFING PRODUCT APPROVAL. |
| |
| 5) FRENCH DOOR PRODUCT APPROVAL, NOTICE |
| OF ACCEPTANCE # 99-0902.04 STATES THAT |
| A HURRICANE PROTECTION SYSTEM IS |
| REQUIRED.SPECIFY EITHER IMPACT |
| RESISTANT DOORS OR HURRICANE MISSILE |
| IMPACT PROTECTION SHUTTERS.IF SHUTTERS |
| ARE TO BE USED, HOW WILL THE OCCUPANTS |
| GET BACK INTO THE BUILDING AFTER |
| INSTALLATION? |
| |
| 6) CASEMENT WINDOWS G, L AND M.TWO |
| DIFFERENT PRODUCT APPROVALS, BOTH PGT |
| (NOA # 00-0804.03 AND 01-1108.07), WERE |
| SUBMITTED AS SINGLE COPIES.ADVISE |
| WHICH IS TO BE USED AND SUBMIT AN |
| ADDITIONAL COPY. |
| |
| 7) SINGLE HUNG WINDOW PRODUCT APPROVAL |
| NOTICE OF ACCEPTANCE # 01-0629.08 OFFERS |
| TWO GLAZING OPTIONS, BOTH SINGLE GLAZED. |
| THE WINDOW SCHEDULE PROPOSES DOUBLE |
| GLAZED UNITS FOR WINDOWS I AND J.THESE |
| ARE OUTSIDE THE SCOPE OF THE SUBMITTED |
| PRODUCT APPROVAL. |
| |
| 8) FBC 2101.3.1SPECIFY WINDOW AND DOOR |
| LINTELS. |
| |
| 9) FBC 2405.2THE FRENCH DOOR GLAZING |
| IS IN A 'HAZARDOUS LOCATION' AND IS |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201).SUBMIT DETAILS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 10) FBC 2309.6ACCESS TO THE ATTIC. |
| AN INTERIOR ACCESS OPENING NOT LESS THAN |
| 20X36 INCHES SHALL BE PROVIDED. |
| |
| 11) FBC 2309.7VENTILATION OF ATTIC |
| SPACE.PROVIDE CROSS VENTILATION USING |
| SCREENED VENTS WITH A TOTAL AREA NOT |
| LESS THAN 1/150 OF THE CEILING AREA. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |