Plan Review Notes
Plan Review Notes For Permit 02051906
Permit Number 02051906
Review Stop P
Sequence Number 1
Notes
Date Text
2002-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) A SERVICE SINK AND DRINKING FOUNTAIN
 ARE REQUIRED FOR MINIMUM FIXTURE REQUIRE
 MENT TABLE 403.1 GIVE DETAIL FOR D.F.
 PER 11-4.24
 2) SHT P-1 KEYNOTES #2 2-1/2" AND SMALL-
 ER PIPE SHALL HAVE A MINIMUM SLOPE OF
 1/4" PER FOOT. TABLE 704.1
 3) SHT A3 URNAL PER 11-4.18 URNAL LIP
 SHALL BE 1'5" AFF AND HAVE A MINIMUM
 FLOOR SPACE OF 30"X48". PLEASE SHOW ON
 PLANS.
 4) SHT A3 WATER CLOSETS SHALL BE SET
 1'6" TO CENTER OFF WALL. PLEASE SHOW ON
 PLANS.
 5) SHT A3 DETAIL 4 KITCHEN/LOUNGE SINK
 SHALL COMPLY WITH 11-4.24. EITHER SHOW
 CLEAR FLOOR SPACE FOR PARALLEL APPROACH
 OR SHOW DETAIL FOR KNEE CLEARANCE 4.24.3
 EXPOSED PIPES 4.24.6 ECT. COUNTER SHALL
 BE MAX. 2'10" AFF 4.24.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377