Plan Review Notes
Plan Review Notes For Permit 02051906
Permit Number 02051906
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-06-19 00:00:001) EXITING NOTED VIA KITCHEN/LOUNGE 100.
 EXITING VIA A KITCHEN IS NOT
 ALLOWED. PLEASE RECONSIDER THE NAME OF
 THIS ROOM OR PROVIDE ANOTHER EXIT
 LOCATION.
  
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910