Plan Review Notes
Plan Review Notes For Permit 02051829
Permit Number 02051829
Review Stop E
Sequence Number 2
Notes
Date Text
2003-01-23 00:00:00*********** UNSAT ****************
  
 PLEASE NOTE, PLANS HAVE BEEN REVISED
 FROM ORIG SUBMITTAL AND HAVE CHANGED
 ELECTRICAL RISER AND LAYOUT. PLEASE SEE
 THE FOLLOWING COMMENTS.
  
 1)NOTE: PLEASE SEE FLOOR PLAN, SHOWS
 PANELS "A" AND "T",PLEASE SEE RISER
 DIAGRAM, SHOWS "LA" & "LB? PLEASE SEE
 PANEL SCHEDULES SUBMITTED, SHOWS "LA"
 "T" AND "M"?? PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE 384-16 FOR MCB REQ`D
 ON SECCONDARY SIDE OF TRANSFORMER FOR
 LIGHTING/APPL PANEL.
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING PER
 220-12B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy