Plan Review Notes
Plan Review Notes For Permit 02051829
Permit Number 02051829
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-11 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE ARE CALCUALTIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 PROVIDE MANUFACTURER INSTALLATION DATA
 FOR THE CONDENSER UNIT STANDS OR
 ENGINEERED DETAIL.
  
 WHERE EQUIPMENT & APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS AT A
 HEIGHT EXCEEDING 16 FT SHALL HAVE A
 PERMANENT MEANS OF ACCESS.2001 FBC(M)
 306.5.
  
 INDICATE ALL NEW OR EXISTING FIRE
 DAMPERS ON PLAN AS PER 2001 FBC(M)
 607.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.