2002-06-05 00:00:00PLEASE PROVIDE A DETAILED ENGINEERING
 ANALYSIS FOR THE ADDED FLOOR LOADING OF
 THE PROPOSED FOUR INCHES OF CONCRETE.
 SEE FBC 1601.2.
  
 THE RAISED AREAS ARE REQUIRED TO BE
 HANDICAP ACCESSIBLE.SEE FBC
 11-4.1(1)(A)
  
 DOORS #4,#5,#6, AND #7 DO NOT HAVE THE
 MANEUVERING CLEARANCE REQUIED BY FBC
 11-4.13.6