Plan Review Notes For Permit 02051749
Permit Number 02051749
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-31 00:00:00UNSAT
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REFER TO FS/FAC 553.79(6)(A) AND
 RESUBMIT UNDER SAME.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR AT
 THE 600 AMP DISCONNECT IS INCORRECT FOR
 PARALLEL 350 MCM. PLEASE REFER TO TABLE
 250-66.
  
 2} THERE SHOULD NOT BE A NEUTRAL TO THE
 PRIMARY OF THE TRANSFORMER.
  
 3} PLEASE INDICATE WHERE THE GEC IS
 LOCATED FOR THE SEPERATELY DERIVED
 SYSTEM PER 250-30.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW