Plan Review Notes For Permit 02051749 |
Permit Number |
02051749 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-31 00:00:00 | UNSAT | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE REFER TO FS/FAC 553.79(6)(A) AND | | RESUBMIT UNDER SAME. | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR AT | | THE 600 AMP DISCONNECT IS INCORRECT FOR | | PARALLEL 350 MCM. PLEASE REFER TO TABLE | | 250-66. | | | | 2} THERE SHOULD NOT BE A NEUTRAL TO THE | | PRIMARY OF THE TRANSFORMER. | | | | 3} PLEASE INDICATE WHERE THE GEC IS | | LOCATED FOR THE SEPERATELY DERIVED | | SYSTEM PER 250-30. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT.8392 |
|