2002-09-09 00:00:00 | DENIED:2ND REQUEST |
| |
| PLAN INDOCATS 4 A/C SYSTEMS & EQUIPMENT |
| SCHEDULE REFLECTS 3 A/C SYSTEMS. |
| PROVIDE EQUIPMENT INFORMATION FOR A/C |
| #2. |
| |
| MECHANICAL PLAN DOES NOT COINCIDE WITH |
| THE A-2 FLOOR PLAN - AHU'S 3 & 4 ARE |
| SHOWN IN OPPOSITE LOCATIONS. |
| |
| BALANCED RETURN AIR - 2001 FBC(M) 601.4 |
| RETURN AIR SHALL BE EQUAL TO SUPPLY |
| AIR BY MEANS OF AIR TRANSFER OR A RETURN |
| AIR (JUMPER). |
| |
| PRIOR TO CONNECTING NEW DUCTWORK TO |
| EXISTING DUCTOWRK, CALL FOR AN |
| INSPECTION. |
| |
| WHERE MULTIPLE AIR-HANDLING SYSTEMS |
| SHARE COMMON SUPPLY OR RETURN AIR DUCTS |
| OR PLENUMS WITH A COMBINED CAPACITY |
| GREATER THAN 2,000 CFM, THE RETURN AIR |
| & SUPPLY SYSTEMS SHALL BE PROVIDED WITH |
| SMOKE DETECTORS IN ACCORDANCE WITH |
| SECTION 606.2.1 OR UPON ACTIVATION, THE |
| SMOKE DETECTORS SHALL SHUT DOWN THE AIR |
| DISTRUBUTION SYSTEM. 2001 FBC(M) 606.2.2 |
| & 606.4. |
| |
| PLEASE NOTE, DUCTS SHALL NOT BE |
| INSTALLED IN OR WITHIN 6 INCHES OF THE |
| GROUND AS PER 2001 FBC(M) 603.12. |
| |