Date Text
2002-09-09 00:00:00DENIED:2ND REQUEST
  
 PLAN INDOCATS 4 A/C SYSTEMS & EQUIPMENT
 SCHEDULE REFLECTS 3 A/C SYSTEMS.
 PROVIDE EQUIPMENT INFORMATION FOR A/C
 #2.
  
 MECHANICAL PLAN DOES NOT COINCIDE WITH
 THE A-2 FLOOR PLAN - AHU'S 3 & 4 ARE
 SHOWN IN OPPOSITE LOCATIONS.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 PRIOR TO CONNECTING NEW DUCTWORK TO
 EXISTING DUCTOWRK, CALL FOR AN
 INSPECTION.
  
 WHERE MULTIPLE AIR-HANDLING SYSTEMS
 SHARE COMMON SUPPLY OR RETURN AIR DUCTS
 OR PLENUMS WITH A COMBINED CAPACITY
 GREATER THAN 2,000 CFM, THE RETURN AIR
 & SUPPLY SYSTEMS SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH
 SECTION 606.2.1 OR UPON ACTIVATION, THE
 SMOKE DETECTORS SHALL SHUT DOWN THE AIR
 DISTRUBUTION SYSTEM. 2001 FBC(M) 606.2.2
 & 606.4.
  
 PLEASE NOTE, DUCTS SHALL NOT BE
 INSTALLED IN OR WITHIN 6 INCHES OF THE
 GROUND AS PER 2001 FBC(M) 603.12.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.