Plan Review Notes For Permit 02051691 |
Permit Number |
02051691 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-08-15 00:00:00 | DENIED: | | | | PLAN INDICATES 4 A/C SYSTEMS & EQUIPMENT | | ONLY REFLECTS 3 A/C SYTEMS.MECHANICAL | | PLAN DOES NOT COINCIDE WITH THE A-2 | | FLOOR PLAN - AHU UNIT 3 & 4 ARE SHOWN | | IN DIFFERENT LOCATIONS. | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | AIR BY MEANS OF AIR TRANSFER OR A | | RETURN AIR (JUMPER). | | | | PRIOR TO CONNECTING NEW DUCTWORK TO | | EXISTING DUCTWORK CALL FOR AN INSPECTION | | | | WHERE MULTIPLE AIR-HANDLING SYSTEMS | | SHARE COMMON SUPPLY OR RETURN AIR DUCTS | | OR PLENUMS WITH A COMBINED CAPACITY | | GREATER THAN 2,000 CFM, THE RETURN AIR | | & SUPPLY SYSTEM SHALL BE PROVIDED WITH | | SMOKE DETECTORS IN ACCORDANCE WITH | | SECTION 606.2.1 OR UPON ACTIVATION, THE | | SMOKE DETECTORS SHALL SHUT DOWN THE AIR | | DISTRIBUTION SYSTEM. 2001 FBC(M) 606.2.2 | | & 606.4 | | | | PLEASE NOTE DUCTS SHALL NOT BE INSTALLED | | IN OR WITHIN 6 INCHES OF THE GROUND AS | | PER 2001 FBC(M) 603.12. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|