Plan Review Notes For Permit 02051691 |
Permit Number |
02051691 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-08-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE STILL | | NOT CLEAR AND NOT SHOWING ENOUGH | | INFORMATION FOR REVIEW. | | | | 2)NOTE: PLEASE NOTE NO MAIN SHOWN ON | | PANEL "A" AT MAIN HOUSE. | | OR ARE MAINS GROUPED PER 230-72. | | | | 3)NOTE: PLEASE NOTE NO GROUNDING SHOWN | | AT MAIN HOUSE. | | | | 4)NOTE: PLEASE CLARIFY AHU`S AND CU`S | | AT APT W/ 19.1KW OF HEAT?? PLEASE NOTE | | | | 5)NOTE: PLEASE NOTE IF APT AT REAR, | | CLARIFY MIN REQ`D CIRCUITS PER 210-52 | | 210-12 | | | | **** NOTE *** | | PLEASE CALL TO SET A MEETING TO GO OVER | | PLANS AND CORRECTIONS THAT ARE NEEDED. | | PLEASE ALSO SEE ATTACHED SHEET PER FS/ | | FAC 553-80(2)(B) | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|