Plan Review Notes
Plan Review Notes For Permit 02051691
Permit Number 02051691
Review Stop E
Sequence Number 2
Notes
Date Text
2002-07-15 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOW A RISER
 DIAGRAM AND PANEL SCHEDULES ARE
 SUBMITTED. PLEASE NOTE MAIN REQ`D FOR
 MAIN HOUSE.225-31
  
 2)NOTE: PLEASE NOTE NO GROUNDING DETAIL
 FOR MAIN HOUSE. 250-32
  
 3)NOTE: PLEASE NOTE THAT LOAD CALCS DO
 NOT CORRELATE WITH AHU LOADS SHOWN.
 PLEASE SEE PANELS/LOADS.
  
 4)NOTE: PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTER-SPACE NEED TO
 BE GFI/GFI PROTECTED.210-8-A-6
  
 5)NOTE: PLEASE NOTE THAT THE TWO LOADS
 ADDED FROM BATH PANELS AT MAIN HOUSE
 EXCEED THE 200A RATING OF MAIN. PLEASE
 INCREASE SERVICE OR IT APPEARS LOAD
 CALCS NEED TO BE REDONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 CALLED AND SPOKE TO ARCH ON FRIDAY JULY
 12TH. WENT OVER ITEMS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372