Plan Review Notes
Plan Review Notes For Permit 02051645
Permit Number 02051645
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-21 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-DIRECT ENTRY FROM GARAGE TO BONUS BED-
 ROOM IS NOT ALLOWED BY SEC. 411.2.8
 FBC 2001.
 3-24SH WINDOW SIZE TYP. DON'T PROVIDE
 THE MIN 24" CLEAR HEIGHT & 5.7 S.F.
 CLEAR OPENING REQ'D BY SEC. 1005.4.4
 FBC 2001. IS THIS CUSTOM MADE WINDOW?
 4-REVISE A/C AREA IN ENERGY CALCULATIONS
 TO MATCH ARCHITECTURAL PLANS.
 5-SPECIFY FIRECUTS AT MASONRY WALL AS
 REQ'D BY SEC. 2305.4 FBC 2001.
 6-PROVIDE SPECS TO PROTECT SOIL & FOOT'G
 FROM WATER FALLING FROM ROOF VALLEYS.
 SEC. 1804.1.6 FBC 2001.
 7-PROVIDE SOIL TEST REPORT.
 8-PROVIDE DESIGN OF JOINTS @ CONC. SLAB.
 SEC. 1909.3 FBC 2001 (OR SPECIFY WWM
 SUPPORTS. SEE EXCEPTION ON SEC. 1909.3
 9-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN. SEE ATTACHED CITY SAMPLE
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS & ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS AS SHOWN ON PLANS.
 B)COMPLETE DADE COUNTY PRODUCT APPROVAL
 FOR "PAN AMERICAN" WINDOW MULLIONS
 SINCE WINDOWS ARE FROM PAN AMERICAN.
 11-PROVIDE UPDATED ORIGINAL LETTER FOR
 MASONRY TO BE USED. LETTER ADDRESSED
 TO CITY OF WPB. IDENTIFY PROJECT AND
 CONTRACTOR.
 12-SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT STAIRS. SEC. 2305.1.4 FBC.
 13-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION @ 2ND FL FRAMING PLAN AS
 REQ'D BY SEC. 2305.2.2 FBC 2001.