2002-06-21 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-DIRECT ENTRY FROM GARAGE TO BONUS BED- |
| ROOM IS NOT ALLOWED BY SEC. 411.2.8 |
| FBC 2001. |
| 3-24SH WINDOW SIZE TYP. DON'T PROVIDE |
| THE MIN 24" CLEAR HEIGHT & 5.7 S.F. |
| CLEAR OPENING REQ'D BY SEC. 1005.4.4 |
| FBC 2001. IS THIS CUSTOM MADE WINDOW? |
| 4-REVISE A/C AREA IN ENERGY CALCULATIONS |
| TO MATCH ARCHITECTURAL PLANS. |
| 5-SPECIFY FIRECUTS AT MASONRY WALL AS |
| REQ'D BY SEC. 2305.4 FBC 2001. |
| 6-PROVIDE SPECS TO PROTECT SOIL & FOOT'G |
| FROM WATER FALLING FROM ROOF VALLEYS. |
| SEC. 1804.1.6 FBC 2001. |
| 7-PROVIDE SOIL TEST REPORT. |
| 8-PROVIDE DESIGN OF JOINTS @ CONC. SLAB. |
| SEC. 1909.3 FBC 2001 (OR SPECIFY WWM |
| SUPPORTS. SEE EXCEPTION ON SEC. 1909.3 |
| 9-STORM SHUTTERS: |
| A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| AND KEY PLAN. SEE ATTACHED CITY SAMPLE |
| B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS & ANCHOR TYPE AND |
| SPACING TO BE USED ACCORDING TO THE |
| MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| EDGE DISTANCE, PANEL SPAN, CONNECTION |
| TYPE AND STRUCTURE TO BE ATTACHED TO. |
| 10-PROVIDE PRODUCT APPROVAL FOR: |
| A)ENTRY DOORS AS SHOWN ON PLANS. |
| B)COMPLETE DADE COUNTY PRODUCT APPROVAL |
| FOR "PAN AMERICAN" WINDOW MULLIONS |
| SINCE WINDOWS ARE FROM PAN AMERICAN. |
| 11-PROVIDE UPDATED ORIGINAL LETTER FOR |
| MASONRY TO BE USED. LETTER ADDRESSED |
| TO CITY OF WPB. IDENTIFY PROJECT AND |
| CONTRACTOR. |
| 12-SPECIFY FIREBLOCKING MATERIAL AND |
| LOCATION AT STAIRS. SEC. 2305.1.4 FBC. |
| 13-SPECIFY DRAFSTOPPING MATERIAL AND |
| LOCATION @ 2ND FL FRAMING PLAN AS |
| REQ'D BY SEC. 2305.2.2 FBC 2001. |