2002-10-29 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-REVISE TRUSS ANCHOR SCHEDULE TO MATCH
 USP CATALOGUE OR PROVIDE ENGINEERING
 CALCS FOR DIFFERENT VALUES. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE COMPLETE UL SPECIFICATIONS FOR
 ONE HR FIRE RATED GLASS BLOCK ASSEMBLY
 AS REQUIRED BY TABLE 600 FBC 2001.
 **ALSO, PRODUCT APPROVAL TO BE LEGIBLE.
 **NOTE: GLASS BLOCK TO BE SAFETY GLASS
 IF FACE THICKNESS IS LESS THAN 0.25"
 SEC. 2405.2.2 FBC 2001.
 4-FLOOD ZONE A8. WILL NEED TO PROVIDE
 THE ELEVATION CERTIFICATE AS REQUIRED
 BY FEMA.