Plan Review Notes
Plan Review Notes For Permit 02051644
Permit Number 02051644
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-20 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE SIZE OF ATTIC ACCESS. NOTE #14.
 36" MIN.(NOT 30"). SEC. 2309.6 FBC.
 3-CLARIFY SIZE OF EGRESS WINDOWS. 24SH &
 34SH DON'T PROVIDE 24" MIN. CLEAR HT.
 ALSO, 24SH DON'T PROVIDE THE 5.7 S.F.
 MIN. CLEAR OPENING. SEC 1005.4.4 FBC
 4-SEE COMMENTS ON PLANS. PLEASE RETURN
 REVIEWED SET TO EXPEDITE REVIEW.
 5-SPECIFY FIRECUTS AT MASONRY WALL AS
 REQUIRED BY SEC. 2305.4 FBC 2001.
 6-PROVIDE SPECIFICATIONS FOR SOIL AND
 FOOTING PROTECTION WHEN IMPACTED BY
 WATER FROM VALLEYS. SEC. 1804.1.6 FBC.
 7-PROVIDE SOIL TEST REPORT.
 8-DESIGN JOINTS AT CONCRETE SLAB. SEC.
 1909.3 FBC. (OR SPECIFY WWM SUPPORTS.
 SEE SEC. 1909.3 FBC 2001).
 9-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS & ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 10-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE ENTRY DOOR AS SHOWN ON PLANS.
 B)COMPLETE DADE COUNTY PRODUCT APPROVAL
 FOR PAN AMERICAN WINDOW MULLIONS SINCE
 WINDOWS USED ARE PANAMERICAN NO LAWSON
 C)ARCHED WINDOWS NEED LEGIBLE DRAWINGS.
 11-PROVIDE UPDATE ORIGINAL LETTER OF
 MASONRY TO BE USED. LETTER TO BE
 ADDRESSED TO CITY OF WPB CLEARLY
 IDENTIFYING PROJECT AND CONTRACTOR.
 12-PROVIDE 2X STRUCTURAL BUCK DETAIL AS
 REQ'D BY PRODUCT APPROVAL SUBMITTED
 FOR ARCHED WINDOWS.
 13-AREA CALCULATIONS DON'T MATCH. SEE
 SHEET C-1 AND A-1. REVISE AS REQUIRED.
 14-BRING BACK DWGS TO PALM BEACH COUNTY
 TO HAVE A/C AREAS REVISED AS REQUIRED.
 15-NEED A COMPLETE BATHRM @ 1ST FL. WITH
 DOOR WITH 29" MIN. CLEAR OPEN'G.
 MASTER BATHRM WATER CL. DOOR DOESN'T
 PROVIDE IT. (NOTE: POWDER RM DOESN'T
 COUNT AS BATHRM) SEC 11-11 FBC 2001.
 16-PROVIDE COMPLETE DETAILS & UL SPECS
 FOR 1HR FIRE RATED GLASS BLOCK
 ASSEMBLY AT ZERO LOT LINE WALL. AS
 REQ'D BY TABLE 600 FBC 2001.
 17-TRUSS ANCHOR SCHEDULE & ROOF FRAMING
 PLAN DON'T MATCH REVISE & CLARIFY.
 18-WHERE IS THE ROOF SHEATHING NAILING
 SCHEDULE? NO SHOWN ON PLANS.
 19-GABLE END DETAIL IS MISSING SOME
 CONNECTORS. ALSO, VERIFY THAT GABLE
 END IS STRUCTURAL CONTINUOUS AS REQ'D
 BY SECTION 2313.4 FBC 2001.
 20-REVISE ENERGY CALCULATIONS TO MATCH
 A/C AREAS THAT MATCH THIS HOUSE. SEE
 SHEET A-1.